G
®
HYGRASREG
KH - 40 ⁄ AH - 40
Electronic hygrostat and humidity sensor HYGRASREG
displaying ACTUAL humidity (accuracy class ± 3 % r.H.) and for setting the target humidity.
It is suitable for controlling and monitoring the relative air humidity, e.g. in ventilation and air conditioning ducts, laboratories, production rooms,
climatic exposure test cabinets, swimming pools, greenhouses etc., for controlling humidifying and dehumidifying facilities. The measuring transducers
are designed for exact detection of humidity. The KH - 40 ⁄ AH - 40 uses a digital, long-term stable sensor as a measuring element for measuring
humidity. It is used in dust-free, unpolluted, non-aggressive air.

TECHNICAL DATA

Power supply:
Power consumption:
Sensors:
Sensor protection:
Setting range:
Output:
Deviation, humidity:
Ambient temperature:
Long-term stability:
Enclosure:
Enclosure dimensions:
Electrical connection:
Cable gland:
Protective tube:
Prozessanschluss:
Protection class:
Protection type:
Standards:
Display:
Displaying:
FUNCTION
®
HYGRASREG
KH - 40 – Duct hygrostats and humidity sensors (± 3 %), Premium
®
HYGRASREG
AH - 40 – On-wall hygrostats and humidity sensors (± 3 %), Premium
Type ⁄ WG02
KH - 40 - U
K H - 4 0 W T Y R -1 D I S P L AY
AH - 40 - U
A H - 4 0 W T Y R -1 D I S P L AY
Accessories
SF-M
®
KH - 40 ⁄ AH - 40 with one switching output, adjustable switching threshold and display for
24 V AC (± 20 %); 15...36 V DC
< 1.1 VA ⁄ 24 V DC ; < 2.2 VA ⁄ 24 V AC
digital humidity sensor, small hysteresis, high long-term stability
plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable
(optional metal sinter filter, Ø 16 mm, L = 32 mm)
5...95 % r. H.
potential-free changeover contact (24 V), 1 A ohmic load
± 3 % r. H. (20...80 %); at + 20 °C, otherwise ± 5 % r. H.
storage –35...+85 °C;
operation – 30...+75 °C, non-precipitating
± 1 % per year
plastic, material polyamide, 30 % glass-globe-reinforced,
with quick-locking screws (slotted ⁄ Phillips head combination),
colour traffic white (similar to RAL 9016), enclosure cover for display is transparent!
72 x 64 x 43.3 mm (Tyr 1 with display)
0.14 - 1.5 mm², via terminal screws
M 16 x 1.5, including strain relief, exchangeable, max. inner diameter 10.4 mm
KH - 40: PLEUROFORM
TM
, material polyamide (PA6), with torsion protection,
Ø 20 mm, NL = 235 mm, v
max
AH - 40: stainless steel, Ø 16 mm, NL = 55 mm
KH - 40: by mounting flange, plastic (included in the scope of delivery)
AH - 40: by screws
III (according to EN 60 730)
IP 65 (according to EN 60 529) enclosure only!
CE conformity, electromagnetic compatibility according to EN 61 326,
EMC directive 2014 ⁄ 30 ⁄ EU
two-line display with illumination, cutout approx. 36 x15 mm (W x H),
for displaying actual humidit and for setting the target humidity
The 1st line of the display shows the relative humidity.
The 2nd line shows on the left side the information regarding the switching status of the relay (as a circuit),
as well as the switching value readout in % r.H. on the right side (adjustable using the set potentiometer).
○ Circuit, empty
= relay in idle state
● Circuit, full
= relay energised
The relay output is triggered (contact 13 -11 closed)
if the humidity switchpoint is not reached and opens (contact 12 -11 closed)
in the event of a fault (power failure, condensation)
LED short pulses = relay active → switchpoint not reached
LED long pulses = relay inactive → switchpoint exceeded
Setting Range
Output
Humidity
5...95 % r. H.
1 x Changeover contact
5...95 % r. H.
1 x Changeover contact
Metal sinter filter, Ø 16 mm, L = 32 mm, exchangeable
stainless steel (VA 1.4404)
= 30 m/s (air) (on request, optional stainless steel, Ø 16 mm)
Steps
one-step
one-step
Rev. 2017 - V12 GB
Display
Item No.
12 02-3065- 0221- 000
12 02-1065- 0221- 000
7000-0 050-2200- 100