8.8.- Reset Options (F08)
According to the regulations in force, the reset key must not be functional during the
triggering state. In some geographic zones is required the opposite.
•
001 - The Reset key is not working during the triggering state (value by default).
•
002 - The Reset Key is working during the triggering state.
8.9.- Cross zones function (F09)
The Automatic extinguishant process starts when there is more than one zone in alarm
GB
(Cross zone concept) in our case, with Z1 and Z2, but ocasionally it is possible to
require the activation from a different combination of zones. The combinations alowed
by the extinguishant panel are:
•
001 - Z1 and Z2 (default value).
•
002 - (Z1 y Z2) or Z3.
•
003 - (Z1 y Z2) or (Z1 y Z3) or (Z3 y Z3).
•
004 - Z1,Z2 and Z3.
8.10.- Alarm Level in zone (F10)
In order to achieve a good compatibility with old systems , where the cross level for
zones and buttons didn't exist, it is possible to configure this value:
•
001 - The cross level causes a fault in the panel (default value).
•
002 - The cross level causes an alarm in the panel.
8.11.- Configuration options of the external input NC/NA (F11)
The external input resting level can be configured modifying this value:
•
001 - The resting level is NA. (value by default).
•
002 - The resting level is NC.
8.12.- Configuration options for the Bottle 1 Surveillance NC/ NA (F12)
The resting level of the "bottle 1 surveillance" can be configured modifying this value:
•
001 - Resting level is NA (by default).
•
002 - Resting level is NC.
8.13.- Configuration options for the Bottle 2 Surveillance NC/ NA (F13)
The resting level of the "bottle 1 surveillance" can be configured modifying this value:
•
001 - Resting level is NA (by default).
•
002 - Resting level is NC.
36