4.2.1- Extinction bottle output (BOTTLE)
The extinguishing panel has an output (labeled as BOTTLE) that activates the solenoid
of the extinction equipment. This output allows a total current of 500 mA.
The wiring of this output(1) must begin in the panel socket and end with the end-of-line
module (2) provided with the panel, this module shall be placed as closely as possible
to the solenoid (3) of the extinction bottle.
GB
In case we don't need to use this output, it is necessary to connect the end-of-line
module in the terminals of the extinction bottle output in order to avoid an output fault
signal from the panel.
Extinction triggering Delay
Just in the lower right part of the panel's circuit, there is a double strip of pins for
programming the delay of the extinction activation (DELAY EXT). it is possible
to program the the delay from 0 to 60 seconds, placing the jumper in the position
corresponding to the desired time. You can perform and advanced programming
placing the jumper in the PROG position.
4.2- Extinction block connection
16