8.3.- Configuration options for the door input (F03)
The parameter P03 specifies the function for the door input. The functions can be:
•
000 - Only for information purpose ( selected by default).
•
001 - Stops the extinction process if the door is opened.
8.4.- Self-check first alarm (F04)
In some geographic zones it is necessary to reset the panel before it notifies the
occurrence of an alarm. Once an alarm is produced, the panel will reset the affected
line. If in few minutes the alarm reappears in this same zone or in another, the normal
alarm process will start.
•
001 - Without Self-check first alarm (selected by default).
•
002 - With self-check first alarm.
8.5.- Configuration of extern input Functions (F05)
The activation of the extern input can have the next functions:
•
001 - Sounders On ( selected by default).
•
002 - Extern Reset
•
003 - Sounders and Buzzer off.
•
004 - Buzzer off.
8.6.- Configuration of Manual triggering buttons (F06)
According to the regulations in force, the Hod or Pause Button has priority over the
Manual triggering button. In some geographic zones is required the opposite.
•
001 - Hold or Pause Button has priority over the Manual Triggering button. ( Selected
by default).
•
002 - Manual Triggering Button has priority over the the hold button.
8.7.- Manual triggering button Delay (F07)
The elapsed time between the activation of the Manual triggerin button and the reial
triggering of the extinction is , by default, the same elapsed time that the existing
between the activated state and the triggered state. This time can be modified to an
immediate triggering (minimum 5 seconds).
•
001 - Temporized Triggering: The time is the same that the existing between
activated state and the triggered state (default value).
•
002 - Immediate triggering: The elapsed time from activated to triggered state is fixed
with a countdown of 5 seconds.