Before handling any other part of the system, please
verify the solenoid is disconnected from the bottle.
A quick test of the system can be performed as follows:
GB
•
Create a fault, such as a loop open circuit or a power failure, and check that the fault
relay operates and the fault is indicated on the LEDs and LCD.
•
Cause an alarm to occur and check that the alarm relay outputs are activated and the
correct sounders operate (after the correct delay, if programmed).
•
Configure the system mode as MANUAL and AUTOMATIC , cause an alarm to occur
in Zone 1 and Zone 2, and check that all the extinction process is generated.
•
Configure the system mode as MANUAL and AUTOMATIC, cause an alam to occure
in Zone 1 and Zone 2, and check that the buttons STOP and ABORT work properly..
•
Configure the system mode as MANUAL and AUTOMATIC and check that if the
Manual triggering button is activated, it works as expected
Note: A power failure may take several minutes to be indicated.
5.3- System Test