2.5- Battery connection
(Optional. Module required)
The monoxide panels require two 12V batteries. The housing takes 12V 2.3A/h and
12V 7A/h batteries for the central units. The batteries must be connected in series for
the proper functioning of the panel.
The cable supplied with the unit must be connected so that the positive terminal of one
battery is connected with the negative terminal of the other.
GB
The batteries are placed in the bottom of the box, in the space reserved for this purpose.
Place the 12V 2.3A/h batteries horizontally or the 12V 7A/h batteries vertically.
Connect the wires from the circuit (red and black) to the unused positive and negative
terminals of the two batteries. Remember to connect the batteries together first, using
the battery bridge cable.
10