10 Technical Data

Power supply A1/A2
Voltage range [V]
Rated power [W / VA]
Control circuits, S12 and S22/S32
Rated voltage
Input voltage range
Nominal current / max. peak current per channel
Line resistance per channel
Response time t
, K1 and K2
E
Release time t
, K1 and K2
R
Recovery time t
W
Permissible test pulse duration t
Output circuit
Enabling paths
Contact type
Contact material
Switching voltage Un
Max. thermal permanent current I
Switching capacity
Utilisation category according to
DIN EN 60947-5-1:2005-09-00
Mechanical service life
Short circuit protection
Max. total current  I
² per group at 25°C
n
Max. total current  I
² per group at 55°C
n
Reporting paths 91/92 and Y1/Y2
Contact type
Contact material
Switching voltage Un
Max. permanent current
Reporting path Y03/Y04
Contact type
Switching voltage Un
Max. permanent current
Terminals and connection data
Connection cross sections
− Single-core or finely stranded
− Finely stranded with wire-end ferrule according to
DIN 46228
AWG conductor size (only use Cu wires)
Maximum tightening torque
Stripping length
Safety
Safe separation
Rated voltage
Surge voltage category
Rated surge voltage
Degree of soiling
Basic isolation
Rated voltage
Surge voltage category
Rated surge voltage
Degree of soiling
Electrical isolation between control and reporting
circuits
Doc. # BA000659 – 08/2011 (Rev. B)
Min.
19.2 V
DC 24 V
DC 19.2 V to 26.4 V
50 mA / 200 mA
max. 20 Ω
< 25 ms
< 10 ms
≤ 40 ms
< 1 ms
TP
Group1: 13/14, 23/24, 33/34 and 43/44
Group2: 53/54, 63/64, 73/74 and 83/84
Forced, normally open
Ag - alloy, gold plated
230 V AC
6 A
TH
50 mW to 1,500 VA
AC-15: Ue = 230 V, Ie = 5 A
DC-13: Ue = 24 V, Ie = 5 A
7
10
Fuse max. 6 A gG / fuse integral < 100 A²s
2 x 72 A²
2 x 25 A²
Forced, normally closed
Ag - alloy, gold plated
24 V DC
500 mA
Semiconductor, normally open
24 V DC
20 mA
Screw clamp terminals
1 x 0.14 mm² to 2.5 mm²
2 x 0.14 mm² to 0.75 mm²
1 x 0.25 mm² to 2.5 mm²
2 x 0.25 mm² to 0.5 mm²
26–14
0.5 to 0.6 Nm (5-7 lbf-in)
Enable paths from control and reporting circuits
Enable paths Group1 from enable paths Group2
300 V
IV
6 kV
2 inside, 3 outside
Power circuit from control and reporting circuits (only for AC 115-230V)
300 V
III
4 kV
2 inside, 3 outside
30 V
SNE 4028S
AC/DC 24 V
Type
Max.
26.4 V
2,4 / 4,0
2,7 / 4,4
Spring-loaded terminals
2 x 0.2 mm² to 1.5 mm²
2 x 0.25 mm² to 1.5 mm²
(trapezoid crimping)
24–16
max. 8 mm
AC 115-230 V
Min.
Type
Max.
98 V
253 V
2,4 / 5,5
2,7 / 6,0
EN 11