Name
Description
E1-04
For a linear V/f characteristics, set the
Max. Output Freq.
same values for E1-07 and E109. In this
Max. Output Volt-
E1-05
case, the setting for E108 will be disre-
age
garded. Ensure that the four frequencies
E1-06
Base Frequency
are set according to these rules or OPE10
fault will occur:
E1-07
Middle Output Freq.
Max. Output Volt-
E1-04 = E1-06 = E1-07 = E1-09
E1-08
age
04)(E1-06)(E1-07)(E1-09) (E1-10) (E1-
08) (E1-05) (E1-13) Output voltage Out-
E1-09
Min. Output Freq.
put frequency
E1-10
Min. Output Voltage
E1-13
Base Voltage
Motor Data
Motor Rated Cur-
E2-01
Automatically set during Auto-Tuning.
rent
Motor rated slip in hertz (Hz). Automati-
E2-02
Motor Rated Slip
cally set by Rotational Auto-Tuning.
Motor No-Load
Magnetizing current in Ampere. Automat-
E2-03
Current
ically set by Rotational Auto-Tuning.
Number of motor poles. Automatically set
E2-04
Motor Poles
by Auto-Tuning.
Sets the phase-to-phase motor resistance
Motor Line-to-Line
E2-05
in ohms. Automatically set by Auto-Tun-
Resistance
ing.
Sets the voltage drop due to motor leak-
Motor Leakage
E2-06
age inductance as a percentage of motor
Inductance
rated
Digital Input Settings
H1-01
DI S1 to S6 Func-
to
Selects the function of terminals S1 to S6.
tion Selection
H1-06
Major functions are listed at the end of the table.
Digital Output Settings
DO MA/MB Func-
Set the function for the relay output MA-
H2-01
tion
MB-MC
Sets the function for the photocoupler out-
H2-02
DO P1 Function
put P1
Sets the function for the photocoupler out-
H2-03
DO P2 Function
put P2
Major functions are listed at the end of the table.
Analog Input Setting
0:0 to +10 V (neg. input is zeroed)
H3-01
A1 Signal Level Sel.
1:0 to +10 V (bipolar input)
H3-02
A1 Function Sel.
Assign a function to terminal A1
Sets the input value in % at 10 V analog
H3-03
A1 Gain
input
Sets the input value in % at 0 V analog
H3-04
A1 Bias
input
0:0 to +10 V (neg. input is zeroed)
A2 Signal Level
1:0 to +10 V (bipolar input)
H3-09
Selection
2:4 to 20 mA (9 bit input)
3:0 to 20 mA
H3-10
A2 Function Sel.
Assign a function to terminal A2
Sets the input value in % at 10 V/20 mA
H3-11
A2 Gain
analog input
Sets the input value in % at 0 V/0 mA/4
H3-12
A2 Bias
mA analog input
Analog Input Setting
Par
Name
AM Monitor Selec-
H4-01
tion
AM Gain
H4-02
AM Bias
H4-02
(E1-
Pulse Input Setting (Free. ref. input)
H6-02
RP Input Scaling
Pulse Train Input
H6-03
Gain
Pulse Train Input
H6-04
Bias
H6-06
MP Monitor Sel
H6-07
MP Monitor Scaling
Motor Overload
L1-01
Prot. Sel
Motor Overload
L1-02
Prot. Time
Stall Prevention
L3-01
Selection during
Acceleration
Stall Prev. Level
L3-02
during Accel.
Stall Prev. Selection
L3-04
during Decel.
Stall Prev. Selection
L3-05
during Run
Stall Prev. Level
L3-06
during Run
Auto-Tuning Mode
T1-01
Selection
T1-02
Rated Power
Rated Voltage
T1-03
T1-04
Rated Current
T1-05
Base Frequency
T1-06
Motor Poles
Base Speed
T1-07
Motor Iron Loss
T1-11
Monitor
U1-01
U1-02
U1-03
U1-05
U1-06
Description
Enter value equal to U1- ???? monitor
values. Example: Enter "103" for U1-03.
Sets terminal AM output voltage equal to
100% monitor value.
Sets terminal AM output voltage equal to
0% monitor value.
Sets the number of pulses (in Hz) that is
equal to 100% input value
Sets the input value in % at pulse input
with H6-02 frequency
Sets the input value in % at 0 Hz pulse
input frequency
Pulse Output Setting
Enter value equal to U U??-???? mon-
itor values. Example: Enter "102" for U1-
02.
Sets the number of output pulses when the
monitor is 100% (in Hz).
Motor Overheat Protection
Sets the motor overload protection.
0:Disabled
1:Standard fan cooled motor
2:Standard blower cooled motor
3:Vector motor
Sets the motor overload protection time in
min. Normally no change is necessary.
Stall Prevention
0:Disabled - Motor accelerates at active
acceleration rate and may stall with too
heavy load or too short accel time.
1:General Purpose - Hold acceleration
when current is above L3-02.
2:Intelligent - Acceleration in the shortest
possible time.
Sets the current level for stall prevention
during acceleration.
0:Disabled - Deceleration as set. OV
might occur.
1:General Purpose - Deceleration is
hold if DC bus voltage rises high.
0:Disabled - Motor stall or overload might
occur.
1:Decel Time 1 - Reduce speed using
C1-02.
Sets the current level at which stall pre-
vention during run starts to operate.
Auto-Tuning
0:Rotational Auto-Tuning
2: Terminal resistance only
3: Rotational Auto-Tuning for Energy
Saving
Sets the motor rated power (kW).
Sets the motor rated voltage (V).
Sets the motor rated current (A).
Sets the motor base frequency (Hz)
Sets the number of motor poles
Sets the motor base speed (RPM).
Iron loss for determining the Energy Sav-
ing coefficient. If unknown leave it on
default.
Description
Frequency Reference (Hz)
Output Frequency (Hz)
Output Current (A)
Motor Speed (Hz)
Output Voltage Reference (Vac)