Connection Options; Double Pumps; Put Into Operation - Wilo Yonos MAXO/-D Notice De Montage Et De Mise En Service

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 18
6.3

Connection options

Fig. 
12
3~ 400 V without neutral conductor N: Upstre-
am power transformer.
6.4

Double pumps

Only operate as main and standby pump with automatic
fault-actuated switchover:
Individually connect and secure both motors.
Provide separate switchgear.
Make the identical settings.
6.5
Collective fault signal (SSM)
The contact of the collective fault signal (potential-free
normally closed contact) can be connected to a building
automation system. Internal contact is closed in the
following cases:
The pump has zero current.
There is no fault.
The control module has failed.
DANGER
Danger to life through voltage transmission, if mains and
SSM pipe are led together through a 5-wire cable.
Do not connect SSM pipe to protective low voltage.
Use 5 x 1.5 mm² cable.
During connection of the SSM pipe to the network po-
tential:
SSM phase = live wire L1
6.6
Connect
Fig. 
to 
13
19
7

Put into operation

7.1
Venting
1.
Charge the system appropriately and ventilate.
The pump is self-ventilating.
7.2
Adjusting the operating mode
1.
Adjust desired operating mode with operating
knob
Fig. 
.
20
The LED display shows the operating mode (c1, c2, c3)
or the setpoint value in m (at
7.3
Troubleshooting
The red LED lights up when a fault occurs; additionally an
error code will show on the LED display.
Observe detailed instructions on the Internet
page 2.
Put into operation
p-c,
p-v).
D
D
21