5.3
Preparing the installation
Branch off the safety feed ahead of the pump when ins-
talling in feed of open systems (EN 12828).
Complete all welding and brazing tasks.
Flush unit.
Arrange shut-off devices in front of and behind the
pump. Laterally align the shut-off device above the pump
so that the leakage water does not drip on the control
module.
Make sure that the pump can be installed free of mecha-
nical stresses.
Allow a 10 cm distance around the control module so that
it does not overheat.
Observe permissible installation position
When installing outdoor observe detailed inst-
ructions on the Internet
5.4
Align
The motor head must be aligned according to installation
position.
Check permissible installation positions
Dismantle motor head and carefully turn
Do not remove motor from pump housing.
ATTENTION
Damage to the gasket causes leakage.
Do not remove gasket.
5.5
Fig. 
.
5
page 2.
Fig. 
.
5
Fig. 
.
6
Installation
Fig. 
to 
7
10
Flange-end pump PN 6
DN 32
Screw diameter
Strength class
Tightening torque
Screw length
≥ 55 mm
DN 65
Screw diameter
M12
Strength class
Tightening torque
40 Nm
Screw length
≥ 60 mm
Flange-end pump PN 10 and PN 16
(no combination flange)
DN 32
Screw diameter
Strength class
Tightening torque
Screw length
≥ 60 mm
Installation
EN
DN 40
DN 50
M12
≥ 4.6
40 Nm
≥ 60 mm
DN 80
DN 100
M16
≥ 4.6
95 Nm
≥ 70 mm
DN 40
DN 50
M16
≥ 4.6
95 Nm
≥ 65 mm
19