Circuit Diagrams; Connection Terminals; Notes; Technical Data - DOLD SAFEMASTER BO 5988 Manuel D'utilisation

Module d'arrêt d'urgence
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Circuit Diagrams

S11
A3
A1
S12 S21 S23 S22 S12 13 23 33
(+)
PE(-)
13
23
33
A1
S12
S12
S21
S22
S23
K2
X1
X2
K3
X5
X6
t
Y1
v
Y2
A2
S11/A3+
14
24
34
PE
Y1
Y2
X1 X2 X5 X6 14 24 34
(-)
BO 5988.47
S11
A3
A1
S12 S21 S23 S22 S12 13 23
33
(+)
A1
PE(-)
13
23
33
43
S12
S12
S21
S22
K2
S23
X1
K23
X2
X5
K3
X6
Y1
Y2
A2
S11/A3+
14
24
34
44
PE
Y1
Y2
X1
X2
X5 X6
14
24
34
(-)
BO 5988.61
S11/
A3
S12 S21 S23 S22 S12 13 23
A1
(+)
A1
PE(-)
13
23
33
S12
S12
S21
S22
K2
S23
X1
K23
X2
X5
K3
X6
Y1
Y2
A2
S11/A3+
14
24
34
PE
Y1
Y2
X1
X2
X5
X6
14
24
(-)
BO 5988.62

Connection Terminals

Terminal designation
A1, S11/A3 (+)
A2, A4
S12, S22, S23, X2, X5, Y2
PE (-), S11/A3 (+), S21, X1, X6, Y1 Outputs
13, 14, 23, 24, 33, 34, 43, 44, 53,
54, 63, 64
81, 82
81, 82
83, 84
77, 78
77
81
A4
77
81
78
82
78
82
A2
M 7173
63 81 A4
43
53
53
63
81
54
64
82
82
A2
44
54
64
M 7172
33 43
63 83 A4
53
43
53
63
83
44
54
64
84
84
A2
34
44
54
64
M7414_a
Signal designation
+ / L
- / N
Inputs
Forcibly guided NO contacts for
release circuit
only .47:
Forcibly guided indicator output
only .61: indicator output (NC)
only .62: indicator output (NO)
NO contact release delay
Forcibly guided for release circuit

Notes

Jumper assignment for functions:
Activation via On pushbutton / or automatic On function
On push-
Jumper
Function
button
Y1 - Y2
X5 - X6
The output contacts are switches only
after operation of the On pushbutton.
Line fault monitoring at the On pushbutton
Automatic On function for operating
voltage Off/On or after emergency
stop release
M8687
Line fault detection at the On pushbutton:
The output contacts cannot be closed if the On pushbutton is already
closed before the voltage is applied to S12, S22 (also in the event of a line
fault at the On pushbutton).
A line fault at the On pushbutton which occures after activation of the
device is recognized when swichting-on takes place again and closing of
the output contacts is then prevented.
If a line fault occurs at the On pushbutton after the voltage is already
present at S12, S22, undesired activation will take place, because this line
fault does not differ from the normal closing function.
The gold-plated contacts of the BO 5988 also mean that this module is
suitable for switching small loads of 1 mVA ... 7 VA, 1 mW ... 7 W in the ran-
ge 0.1 ... 60 V, 1 ... 300 mA. The contacts also permit the maximum swit-
ching current. However, since the gold plating is burnt off at this current
level, the device is no longer suitable for switching small loads after this.
The PE terminal permits operation of the device in IT systems with insula-
tion monitoring and also serves as a reference point for testing the control
voltage. The internal short-circuit protection will be bridged on DC devices,
if the protective ground is connected to terminal PE.
One or more extension modules BN 3081 or external contactors with
forcibly guided contacts may be used to multiply the number of contacts of
the emergency stop module BO 5988.

Technical Data

Input
Nominal voltage U
N
BO 5988.--/-00:
BO 5988.--/-24:
Voltage range:
at 10 % residual ripple:
at 48 % residual ripple:
Nominal consumption:
Nominal frequency:
Control voltage
at S11:
at S21:
Control current:
Minimum voltage
at terminals S12, S22:
Recovery time:
Output
16
DC 24 V
DC 24 V + AC 24 V
DC 24 V + AC 48 V
DC 24 V + AC 110 V
DC 24 V + AC 230 V
DC 24 V + AC 240 V
either DC 24 is connected to A3-A4 or
the AC voltage to A1-A2
AC 0.8 ... 1.1 U
N
DC 0.9 ... 1.2 U
N
DC 0.8 ... 1.1 U
N
AC: approx. 6 VA, DC: approx. 3 W
50 / 60 Hz
typ. DC + 24 V
0 V
typ. DC 110 mA
DC 21 V with activated device
2 s
A minimum switch-off time of 10 s
must be observed if the line fault
monitoring function at the On push-
button is active
BO 5988 / 22.03.17 en / 846