Function Diagram; Block Diagram; Approvals And Markings; Applications - DOLD SAFEMASTER BO 5988 Manuel D'utilisation

Module d'arrêt d'urgence
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Safety Technique
SAFEMASTER
Emergency Stop Module
BO 5988

Function Diagram

Pushbutton
on
Mains or
emergency-
stop (Off)
*
K1
K2

Block Diagram

A1
A2
A4 S11/A3(+) X1 X2 Y1 Y2 S12 S12 S22
Overvoltage and short
K2
K3
circuit protection
&
K23
24V ...
Mains
PE(-)
S21
All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.
* Short-circuit detection
at On pushbutton
M 6800
13
23
33
43 53 63 81
Monitoring
logic
K2
K3
K2
K3
K2
K3
S23
14 24 34 44 54
M6801_b
• According to
- Performance Level (PL) e and category 4 to EN ISO 13849-1
- SIL Claimed Level (SIL CL) 3 to IEC/EN 62061
- Safety Integrity Level (SIL) 3 to IEC/EN 61508
• Output: max. 6 NO, 1 NC contacts or 1 NO contact for AC 250 V
• 1-channel or 2-channel connection
• Line fault detection at On pushbutton
• Feedback circuit X1-X2 for monitoring external contactors
• Integrated short-circuit and overvoltage protection
• LED displays for channels 1 and 2 and supply
• Removable terminal strips
• Wire connection: also 2 x 1.5 mm
• DIN 46 228-1/-2/-3-4 or 2 x 2.5 mm
• Optionally with release delayed NO contact to 10 min
• Optionally automatic On function after connection of operating voltage
or activation via On pushbutton
• Optionally cross fault detection in emergency stop control circuit
• Optionally dual voltage version
• Width 100 mm

Approvals and Markings

* see variants

Applications

Protection of people and machines
• Emergency stop circuits on machines
• Monitoring of safety gates

Indicators

LED power supply:
LED K2:
LED K3:
only at BO 5988/4_ _,
BO 5988/5_ _:
LED KT2, KT3:
K23
64
82
15
stranded ferruled (isolated),
2
stranded ferruled DIN 46 228-1/-2/-3
2
*
Canada / USA
on, when operating voltage present
on, when supply on relay K2
on, when supply on relay K3
on, when delayed contacts are energized
BO 5988 / 22.03.17 en / 846