Travel calibration
⚠ Before calibrating the gate run, check that the maneuvering area is free from any obstruction and that there are both opening and
closing mechanical stops.
⚠ The mechanical end-stops are obligatory.
Important! During the calibration, all safety devices will be disabled except for the PARTIAL STOP one.
1. From the [ENCODER]
menu, select [Travel
calibr]. Press ENTER to
confirm
3. The gate-leaf will close
until the final strike-point ...
5. Once the procedure is
over, the display will show
[Travel calibr OK] for a few
seconds.
Memory Roll Card
For memorizing user and system configuration data, then using them on another control board.
After memorizing the data, it is best to remove the Memory Roll card while the control board is in operation.
ERROR MESSAGE
Error messages appear on the display
[Encoder - ERROR], [Error!]
[Safety Test - ERROR]
[End Stop - ERROR]
[Cycle time - ERROR]
[Safety - STOP], [C1], [C3], [C4], [C7] or [C8]
<Travel calibr>
Travel calibr
Close
Travel calibr
OK
.
Broken encoder or wrong connection.
Safety devices malfunctioning.
Malfunctioning endstop contacts
Insufficient working time
Malfunctioning safety devices or wrong connection
2. Select [Confirm?
(Yes)] and press
ENTER to confirm.
4. ... then, the gate-
leaf, will open until the
final strike-point.
Travel calibr
Travel calibr
<Confirm?(yes)>
Travel calibr
Open
Memory roll