minute in order to eliminate any risk. If there actually is a short circuit or nearly one in your
installation it is still quite possible that the harbour fuse will react first. This is because an
automatic circuit breaker can react faster than the Vetus Shore Power Protector within the
first 2 msec. if the current taken is much too high. Therefore, you may never use the Power
Protector as a replacement for a fuse!
Note:
If you find this explanation too technical then do not worry, simply select the B character-
istic (see 3 Operating) and set the correct maximum current for the harbour!
6 Technical details
Input voltage range
Consumption
Disconnect current
Current setting range
Switching capacity
Peak current limit
Display
Accuracy
Disconnecting
Temperature range
Connections
Declaration of conformity
We declare that this product conforms to the following directives:
- Low voltage directive: 93/68/EU, NEN-IEC-EN60335-1,
- EMC directive 89/336/EU, EN50081-1 & EN50082-1
16
090901.01
: 195 V AC – 253 V AC / 50Hz – 60Hz.
: nominal 5 VA
: maximum 16 Ampere
: 1 Ampere – 16 Ampere,
from 1 Ampere – 5 Ampere in steps of 0.1 Ampere
from 5 Ampere -16 Ampere in steps of 0.5 Ampere
: max. 4000 VA (Ohmic and weak inductive loading)
max. 1500 VA (inductive loading at a power factor of < 0.4)
: maximum 6 x In with time limit of >2 msec.
: 2x16 alpha-numeric LC-display with background lighting.
Display shows the effective value of the current load taken.
: + or - 10% of the reading
: well within the limits of the B or C characteristic (can be set) of
an automatic circuit breaker in accordance with the EN 60 898
standard applying in the EU but with a minimum switch off delay
of 2 msec.
: 0°C —+40°C.
: screw connectors for connecting all 230 V AC and earth wires.
Shore power protector