DiTemp
Alarm value entry (AL 1):
The default delivery status is "AL 1 = 30 °C".
Tap the
symbol to access the entry level. Use the
value from right to left (ones, tens and hundreds). Confirm each entry by tapping on the
symbol. The display jumps to the next position.
Alarm entry (def):
The default delivery status is "def = oFF".
Tap the
symbol again with the magnetic pen
You are now in the alarm type entry level "def".
It is possible to select the type of alarm for the entered value here.
• HI = all values greater than the set value activate the alarm contact.
• Lo = all values greater than the set value activate the alarm contact.
• oFF = the alarm is switched off.
Hysteresis (HYSt):
The default delivery status is "HYSt = ∆T = 5 K.
Tap the
symbol again with the magnetic pen
You are now in the hysteresis entry level "HYSt".
Here it is possible to enter a two-digit value which specifies the difference between the
switch-on and switch-off point of the alarm.
The maximum settable hysteresis is ∆T = 50 K.
Alarm output (InFo):
The default delivery status is "InFo = oFF".
Tap the
symbol again with the magnetic pen
You are now in the entry level "InFo".
Here it is possible to select a second signal output, e.g. for a
signal lamp, via "on".
Very important!
Check the plausibility of the alarm value entries "AL 1" and the alarm type entry "def" to
prevent permanent operation of the electronic relay.
Exiting programming (End):
Use the
symbol to access the "End" display, tap it again to return to the start of the selec-
tion level and use the
Technical changes reserved
DiTemp with programmable switching outputs (optional)
symbol to reach the normal operating mode.
symbol to enter the desired alarm
t <(>) T
1
2
1
ALARM
L
Switch assignment
- Bat
- Sens
3
INFO
- 25 -