Geberit Mapress 2 Mode D'emploi page 34

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 43
Operating instructions for Mapress pressing collar and adapter for pressing collar
3
Open and remove the pressing collar
CAUTION
Leaky connection due to failed pressing sequence
Ensure that the pressing collar is completely closed after the
pressing sequence
Have any pressing collars that have not closed completely as
well as the adapter for pressing collar and the pressing tool
inspected for damage by an authorized repair shop. Replace any
connections that have not been pressed correctly (do not
attempt corrective pressing)
If there are any burrs on the pressfitting after the pressing
sequence, have the pressing collar and the adapter for pressing
collar inspected by an authorized repair shop
Pressing the pressfitting ø 108 mm
Orientation
The pressing sequence consists of two steps:
• Preliminary pressing with adapter for pressing collar 221 / 321
• Final pressing with adapter for pressing collar 222 / 322
The position of the locking pin in the locking lug indicates the status of the
pressing sequence:
• Position 1: Pressing collar is positioned
• Position 2: After preliminary pressing with adapter for pressing collar 221 / 321
• Position 3: After final pressing with adapter for pressing collar 222 / 322
34
3
2
1