G
®
AERASGARD
ACO
Schematic diagram
1 2 3
NC
12
11
COM
13
NO
NC = Normally Closed
COM = Common
NO = Normally Open
DIP switches
VOC sensitivity
LOW
MEDIUM (default)
HIGH
VOC automatic zero point
deactivated
activated (default)
CO
content
2
0...2000 ppm (default)
0...5000 ppm
CO
automatic zero point
2
deactivated
activated (default)
Relay assignment
CO
(default):
600...1900 ppm / 900...4700 ppm
2
VOC:
10...95 %
Temperature:
–23...+74 °C
Humidity:
10...95% r.H.
Output
Voltage 0 -10 V (default)
Current 4...20 mA
Note: DIP 5 is not assigned!
- W (with display) ⁄ ALQ - CO
2
OFFSET
CO ² VOC
ON
1 2 3
Reset VOC
Output air quality (VOC)
4
Output temperature in °C
5
6
Output humidity in % r.H.
AFTM - LQ - CO
DIP 1
OFF
O N
OFF
DIP 7
OFF
O N
OFF
O N
- W ⁄ AFTM - CO
2
AFTM - LQ - CO
2
°C
r.H.
ON
ON
4 5 6
7 8 9
DIP
DIP
DIP
VOC
CO ²
mode
CO ²
SET
relay
SET-Setting relay
switchpoint
Humidity table
MR: 0...100 % r. H.
%
2
r.H.
DIP 2
0
OFF
5
OFF
10
O N
15
20
DIP 3
25
OFF
30
O N
35
DIP 4
40
OFF
45
O N
50
55
DIP 6
Continued at the right ...
OFF
O N
DIP 8
Temperature table
MR: –35...+80 °C
OFF
°C
OFF
O N
– 35
O N
– 30
– 25
DIP 9
– 20
OFF
– 15
O N
– 10
– 5
0
+ 5
+ 10
+ 15
+ 20
Continued at the right ...
12
⁄ AFTM - LQ - CO
2
2
U
I
%
A
A
r.H.
in V
in mA
60
0
4.0
65
0.5
4.8
1.0
5.6
70
1.5
6.4
75
2.0
7.2
80
2.5
8.0
85
3.0
8.8
90
3.5
9.6
95
4.0
10.4
100
4.5
11.2
5.0
12.0
5.5
12.8
U
I
°C
A
A
in V
in mA
0.0
4.0
+ 25
0.4
4.7
+ 30
0.9
5.4
+ 35
1.3
6.1
+ 40
1.7
6.8
+ 45
2.2
7.5
+ 50
2.6
8.2
+ 55
3.0
8.9
+ 60
3.5
9.6
+ 65
3.9
10.3
+ 70
4.3
11.0
+ 75
4.8
11.7
+ 80
Rev. 2017 - V20 GB
U
I
A
A
in V
in mA
6.0
13.6
6.5
14.4
7.0
15.2
7.5
16.0
8.0
16.8
8.5
17.6
9.0
18.4
9.5
19.2
10.0
20.0
U
I
A
A
in V
in mA
5.2
12.3
5.7
13.0
6.1
13.7
6.5
14.4
7.0
15.1
7.4
15.8
7.8
16.5
8.3
17.2
8.7
17.9
9.1
18.6
9.6
19.3
10.0
20.0