Configuration
point
Kan.X man.T.comp.
y/n
(pH or Cl/Cd/Pa only)
Ch. X Source Temp.
Kan. X Temp.
connection type
10.3.2
Versatronic cooling water
This table only applies to Ci- or Cr-measurement in the cooling water configuration
(see
Ä Chapter 5.2 'Material code' on page 16)
Configuration item
KT X designation
KT X W-
KT X hyst. W +
KT X hyst. Ws
KT X Dos.duration BIOZ. 1
KT X Dos.duration BIOZ. 2
(only at C1) *
Selection/configuration
yes
No
Analogue inputs
*IN4-temperature input 1
*IN5 temperature input 2
..
....
IN11 Universal input. 2
uncomp.*IN11
Universal input 2 comp.
IN12 Universal input 3 uncomp.
* IN12 Universal input. 3 comp.
* = please only select the marked points!
2-wire
3-wire
Selection/configuration
Text box
Number field
Area: - 99999-99999
Number field
Area: - 99999-99999
Number field
Area: - 99999-99999
Hours minutes seconds
(Hh: mm: ss)
Area: 0-23: 0-59: 0-59
Hours minutes seconds
(Hh: mm: ss)
Area: 0-23: 0-59: 0-59
45
Explanation
The type of temperature
compensation is selected
here.
yes = compensation to a
fixed stored temperature
value.
no = automatic
compensation,
temperature value comes
from the temperature input
that is assigned to the
respective measuring
channel (for assignments
Ä Chapter 4.3 '
see
Allocation of inputs and
outputs to the
measurement channels'
on page 11).
Determining the source for
the temperature display
and for the temperature
compensation of the
respective channel.
With this selection, it is
possible to use the
temperature signal of
another channel for the
display and temperature
compensation of this
channel.
Selection of the
connection type of the
temperature sensor
Explanation
Channel. X Change Name
Choosing the lower
switching point W-
(Underflow of W =
desalination off)
Choice of the upper
switching point W + as a
positive hysteresis of W-
(W + W + = hysteresis + W)
(Excess of W + =
desalination on)
Select the switching point
for the pre-desalination Ws
as a positive hysteresis of
W-
(W + hysteresis Ws = Ws)
(Excess of Ws + Dosage
time points, biocide =
predesalination on)
Determining the metering
time for the metering of
biocide 1
Determining the metering
time for the metering of
biocide 2
417102279 Rev. 2-08.2020
Device menu
Default
yes
Channel 1: IN4
Channel 2: IN5
Channel 3: IN11 comp.
Channel 4: IN12 comp.
3-wire
Default
Name
1600 µS/cm
200 S / cm
(W + = 1800 S /
cm)
100 S / cm
(Ws = 1700 S /
cm)
00:00:10
00:00:10