BFT U-link LEO B CBB 3 400 W01 Instructions D'installation page 17

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 20
TABLE "A" - PARAMETERS MENU - (PARA )
Parameter
min.
max.
Default
0
120
TCA
partial
1
99
opening
1
99
OP. F ORCE
1
99
CLS. F ORCE
Rev. Dis.
0
200
space
0
250
Maintenance
(*) In the European Union, apply standard EN 12453 for force limitations, and standard EN 12445 for measuring method.
TABLE "B" - LOGIC MENU - (LOGIC)
Logic
Definition
Automatic Closing
TCA
Time
Step-by-step
STEP-BY-STEP
movement
MOVEMNT
Pre-alarm
PRE-ALARM
Deadman
HOLD-TO-RUN
Block pulses during
IBL OPEN
opening
Open in other
OPEN IN OTHER
direction
DIRECT.
Configuration of
safety input SAFE 1.
SAFE 1
72
Configuration of
safety input SAFE 2.
SAFE 2
74
INSTALLATION MANUAL
Personal
Definition
10
Automatic closing time [s]
40
Partial opening [%]
Leaf force during opening
80
[%]
Leaf force during closing
80
[%]
0
Reverse disabling space
Programming number of
operations for maintenance
0
threshold
[in hundreds]
Cross
out
Default
setting
used
0
0
 
1
0
1
0
 
2
0
0
 
1
0
1
0
 
2
3
0
0
 
1
0
0
 
1
0
1
0
2
3
 
4
5
6
6
7
8
Waiting time before automatic closing.
Adjusts partial opening percentage compared to total opening in "Partial open" mode.
Force exerted by leaf/leaves during opening. This is the percentage of force delivered, beyond the force
stored during the autoset cycle (and subsequently updated), before an obstacle alarm is generated.
The parameter is set automatically by the autoset function.
WARNING: It affects impact force directly: make sure that current safety
requirements are met with the set value (*). Install anti-crush safety devices
where necessary.
Force exerted by leaf/leaves during closing. This is the percentage of force delivered, beyond the force
stored during the autoset cycle (and subsequently updated), before an obstacle alarm is generated.
The parameter is set automatically by the autoset function.
WARNING: It affects impact force directly: make sure that current safety
requirements are met with the set value (*). Install anti-crush safety devices
where necessary.
Disables obstacle/curb detection near the limit stop in closing
0 = no disabling 200 = disabling Maximum
WARNING: It affects impact force directly: make sure that current safety require-
ments are met with the set value (*). Install anti-crush safety devices where necessary.
Allows you to set a number of operations after which the need for maintenance will be reported
on the AUX output configured as Maintenance or Flashing Light and Maintenance .
Logic not enabled
Switches automatic closing on
Inputs configured as Start E, Start I,
Ped operate with 4-step logic.
Inputs configured as Start E, Start I,
Ped operate with 3-step logic. Pulse
during closing reverses movement.
Inputs configured as Start E, Start I,
Ped operate with 2-step logic. Move-
ment reverses with each pulse.
The flashing light comes on at the same time as the motor(s) start.
The flashing light comes on approx. 3 seconds before the motor(s) start.
Pulse operation.
Deadman mode.
Input 64 is configured as OPEN UP.
Input 65 is configured as CLOSE UP.
Operation continues as long as the OPEN UP or CLOSE UP keys are held down.
WARNING: safety devices are not enabled.
Emergency Deadman mode. Usually pulse operation.
If the board fails the safety device tests (photocell or safety edge, Er0x) 3 times in a row, the device is
switched to Deadman mode, which will stay active until the OPEN UP or CLOSE UP keys are released.
Input 64 is configured as OPEN UP.
Input 65 is configured as CLOSE UP.
WARNING: with the device set to Emergency Deadman mode, safety devices are not enabled.
Pulse operation during opening.
Deadman mode during closing.
Input 64 is configured as PULSE OPEN.
Input 65 is configured as CLOSE UP.
WARNING: safety devices are not enabled during closing.
Pulse from inputs configured as Start E, Start I, Ped has effect during opening.
Pulse from inputs configured as Start E, Start I, Ped has no effect during opening.
Standard operating mode (See Fig.D1).
Opens in other direction to standard operating mode (See Fig.D1).
Input configured as Phot (photocell).
Input configured as Phot test (tested photocell).
Input configured as Phot op (photocell active during opening only).
Input configured as Phot op test (tested photocell active during opening only).
Input configured as Phot cl (photocell active during closing only).
Input configured as Phot cl test (tested photocell active during closing only).
Input configured as Bar, safety edge.
Input configured as Bar, tested safety edge.
Input configured as Bar 8k2.
Description
Optional extras
step-by-step mov.
2 STEP
3 STEP
CLOSED
OPENS
OPENS
DURINg
CLOSINg
OPEN
CLOSES
CLOSES
DURINg
STOP + TCA STOP + TCA
OPENINg
AFTER STOP
OPENS
OPENS
LEO B CBB 3 400 W 01-
4 STEP
OPENS
STOPS
CLOSES
OPENS
17

Publicité

Table des Matières
loading

Table des Matières