Terminal
Definition
40
- REF SWE
42
43
50
51
52
24 Vsafe+
60
Common
61
62
63
Common
64
65
70
Common
71
72
73
74
75
76
Common
77
78
79
80
81
Common
82
83
84
85
Y
ANTENNA
#
Aux logic= 0 - 2ND RADIO CHANNEL output.
Contact stays closed for 1s when 2nd radio channel is activated.
Aux logic= 1 - SCA GATE OPEN LIGHToutput.
Contact stays closed during opening and with leaf open, intermittent during closing, open with leaf closed.
Aux logic= 2 - COURTESY LIGHT command output.
Contact stays on for 90 seconds after the last operation.
Aux logic= 3 - ZONE LIGHT command output.
Contact stays closed for the full duration of operation.
Aux logic= 4 - STAIR LIGHT output.
Contact stays closed for 1 second at start of operation.
Aux logic= 5 - GATE OPEN ALARM output.
Contact stays closed if the leaf stays open for double the set TCA time.
Aux logic= 6 - FLASHING LIGHT output.
Contact stays closed while leaves are operating.
Aux logic= 7 - SOLENOID LATCH output.
Contact stays closed for 2 seconds each time gate is opened.
Aux logic= 8 - MAGNETIC LOCK output.
Contact stays closed while gate is closed.
Aux logic= 9 - MAINTENANCE output.
Contact stays closed once the value set for the Maintenance parameter is reached, to report that maintenance is required.
Aux logic= 10 - FLASHING LIGHT AND MAINTENANCE output.
Contact stays closed while leaves are operating. If the value set for the Maintenance parameter is reached, once the gate has finished moving and the leaf is closed, the contact closes
for 10 sec. and opens for 5 sec. 4 times to report that maintenance is required.
38 -
THALIA P
INSTALLATION MANUAL
Limit switch common
SW 1
Limit switch control motor 1.
SW 2
Limit switch control motor 2.
24V-
Accessories power supply output.
24V+
Tested safety device power supply output (photocell transmitter and safety edge transmitter).
Output active only during operating cycle.
IC 1 and IC 2 inputs common
Configurable command input 1 (N.O.) - Default START E.
IC 1
START E / START I / OPEN / CLOSE / PED / TIMER / TIMER PED
Refer to the "Command input configuration" table.
Configurable command input 2 (N.O.) - Default PED.
IC 2
START E / START I / OPEN / CLOSE / PED / TIMER / TIMER PED
Refer to the "Command input configuration" table.
IC 3 and IC 4 inputs common
Configurable command input 3 (N.O.) - Default OPEN.
IC 3
START E / START I / OPEN / CLOSE / PED / TIMER / TIMER PED
Refer to the "Command input configuration" table.
Configurable command input 4 (N.O.) - Default CLOSE.
IC 4
START E / START I / OPEN / CLOSE / PED / TIMER / TIMER PED
Refer to the "Command input configuration" table.
STOP, SAFE 1 and SAFE 2 inputs common
The command stops movement. (N.C.)
STOP
If not used, leave jumper inserted.
Configurable safety input 1 (N.C.) - Default PHOT.
PHOT / PHOT TEST / PHOT OP / PHOT OP TEST / PHOT CL / PHOT CL TEST / BAR / BAR TEST / BAR 8K2/ BAR OP / BAR OP TEST / BAR 8K2
SAFE 1
OP/ BAR CL / BAR CL TEST / BAR 8K2
Refer to the "Safety input configuration" table.
FAULT 1
Test input for safety devices connected to SAFE 1.
Configurable safety input 2 (N.C.) - Default BAR.
PHOT / PHOT TEST / PHOT OP / PHOT OP TEST / PHOT CL / PHOT CL TEST / BAR / BAR TEST / BAR 8K2/ BAR OP / BAR OP TEST / BAR 8K2
SAFE 2
OP/ BAR CL / BAR CL TEST / BAR 8K2 CL
Refer to the "Safety input configuration" table.
FAULT 2
Test input for safety devices connected to SAFE 2.
SAFE 3 and SAFE 4 inputs common
Configurable safety input 3 (N.C.) - Default PHOT OP.
SAFE 3
PHOT / PHOT TEST / PHOT OP / PHOT OP TEST / PHOT CL / PHOT CL TEST / BAR / BAR/TEST / BAR OP / BAR OP TEST / BAR CL / BAR CL TEST /
Refer to the "Safety input configuration" table.
FAULT 3
Test input for safety devices connected to SAFE 3.
Configurable safety input 4 (N.C.) - Default PHOT CL.
SAFE 4
PHOT / PHOT TEST / PHOT OP / PHOT OP TEST / PHOT CL / PHOT CL TEST / BAR / BAR/TEST / BAR OP / BAR OP TEST / BAR CL / BAR CL TEST /
Refer to the "Safety input configuration" table.
FAULT 4
Test input for safety devices connected to SAFE 4.
SAFE 5 and SAFE 6 inputs common
Configurable safety input 5 (N.C.) - Default PHOT.
SAFE 5
PHOT / PHOT TEST / PHOT OP / PHOT OP TEST / PHOT CL / PHOT CL TEST / BAR / BAR/TEST / BAR OP / BAR OP TEST / BAR CL / BAR CL TEST /
Refer to the "Safety input configuration" table.
FAULT 5
Test input for safety devices connected to SAFE 5.
Configurable safety input 6 (N.C.) - Default BAR.
SAFE 6
PHOT / PHOT TEST / PHOT OP / PHOT OP TEST / PHOT CL / PHOT CL TEST / BAR / BAR/TEST / BAR OP / BAR OP TEST / BAR CL / BAR CL TEST /
Refer to the "Safety input configuration" table.
FAULT 6
Test input for safety devices connected to SAFE 6.
Antenna input.
Use an antenna tuned to 433MHz. Use RG58 coax cable to connect the Antenna and Receiver. Metal bodies close to the antenna can
SHIELD
interfere with radio reception. If the transmitter's range is limited, move the antenna to a more suitable position.
Description
CL.
AUX output configuration