Terminal blocks
Input
Description
OPEN-COM
N.O. OPEN button input for automation control, can be set with DIP1
FOTO-COM
N.C. contact input for safety equipment (photocell)
STOP-COM
N.C. contact input for emergency stop button (STOP)
ANT-COM
Input for integrated RF receiver antenna, frequency 433.92 MHz (Ant: signal - COM: shield)
LAMP/LAMP+24
24V output for warning flasher
Figure 15 shows the holes which can be opened for routing the cables, as required.
Note: Only change the dip switch settings with the door completely closed; alternatively, shut off/restore power to apply
the changed settings.
DIP1: Selects the operating mode of the "Step by step button" and of the transmitter.
ON: Operation: OPEN > STOP > CLOSE > STOP >
OFF: Operation: OPEN > CLOSE > OPEN >
DIP2: Enables or disables automatic closing
ON: Auto close enabled
OFF: Auto close disabled
DIP3: Ramp down speed
ON: Low ramp down speed
OFF: High ramp down speed
DIP4: Enables or disables condominium function.
ON: condominium function enabled. The step-by-step impulse or transmitter impulse has no effect during the opening phase.
OFF: condominium function disabled.
DIP5: Reverse time when closing to tension belt
ON: Minimum time
OFF: Maximum time
DIP6: Reverse when closing to tension belt
ON: Reverse disabled
OFF: Reverse enabled
DIP7: Braking
ON: 80%
OFF: 90%
DIP8: FOTO input
ON: FOTO input enabled when opening and closing
OFF: FOTO input enabled only when closing
The trimmer on the control unit adjusts the sensitivity of the anticrushing sensor.By turning it clockwise the sensitivity of
the sensor is increased and when the trimmer is turned counterclockwise the sensitivity decreases.
After the first sensor intervention the control unit fully opens the leaf ;afterwards (if DIP2=ON) the control unit attempts another
closing maneuver,in case of sensor intervention during this phase the control unit opens the leaf for 3 s and than stops it.
If mains power fails, the door can be operated manually with the rope with the red handle shown in figure 16.
When power is restored, the first command automatically resets the release.
The electronic control unit is designed to program itself and be ready for use as soon as mains power is available.
CAUTION: the self teach procedure requires all safety equipment to be hooked up; if any such equipment is not installed
and hooked up, fit a jumper to the COM -24 V input terminal.
Press PROG. (the courtesy light turns on), then OPEN; the door will close completely. After 2 seconds, it will open to the
full extent desired (press OPEN to set the fully open position).
Now (with Dip 2 ON = auto close enabled) the auto close delay starts; wait for a suitable amount of time to pass, then
press OPEN, the door will close, quit programming mode, and calculate the speeds and decelerations (ramp down) used
during its cycle.
N.B.: the auto close delay is set by the operator, in a range of 0 - 90 seconds. The entire programming procedure is run
at low speed.
ELECTRICAL CONNECTIONS (FIGURE 14)

DIPSWITCH CONFIGURATION

TRIMMER

MANUAL CONTROL

SELF TEACH
17