Introduction; Transport; Handling; Inspection - Parker Hiross Polestar-Smart PST390 Manuel D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

English
2

Introduction

Th is manual refers to refrigeration dryers designed to guarantee high
quality in the treatment of compressed air.

2.1 Transport

Th e packed unit must:
• remain upright;
• be protected against atmospheric agents;
• be protected against impacts.

2.2 Handling

Use a fork-lift truck suitable for the weight to be lift ed, avoiding any type
of impact.

2.3 Inspection

a) All the units are assembled, wired, charged with refrigerant and oil
and tested under standard operating conditions in the factory;
b) on receiving the machine check its condition: immediately notify
the transport company in case of any damage;
c) unpack the unit as close as possible to the place of installation.

2.4 Storage

If several units have to stacked, follow the notes given on the packing.
Keep the unit packed in a clean place protected from damp and bad
weather.
3

Installation

Y
For the correct application of the warranty terms, follow the in-
structions given in the start-up report, fi ll it in and send it back to Seller.
In places with fi re hazard, provide for a suitable fi re-extinguishing sy-
stem.

3.1 Procedures

Install the dryer inside, in a clean area protected from direct atmosphe-
ric agents (including sunlight).
!
For models PST1650-1980 make sure to screw down the stud bolts
in the fl anges before connecting the counterfl anges (see par. 8.6).
Y
Comply with the instructions given in par. 8.2 and 8.3.
All dryers must be fi tted with adequate pre-fi ltration near the dryer air
inlet. Seller is excluded any obligation of compensation or refund for any
direct or indirect damage caused by its absence
Y
Pre-fi lter element (for 3 micron fi ltration or better) must be replaced
at least once a year, or sooner as per manufacturer recommendations.
Y
Correctly connect the dryer to the compressed air inlet/outlet con-
nections.

3.2 Operating space

PST 390-1980
Leave a space of 1.5 m (60 inches) around the unit.
Leave a space of 2 m (80 inches) above dryer models with vertical con-
densation air expulsion.

3.3 Versions

Air-cooled version (Ac)
Do not create cooling air recirculation situations. Do not obstruct the
ventilation grilles.
Water-cooled version (Wc)
If not provided in the supply, fi t a mesh fi lter on the condensation water
inlet.
Y,
Inlet condensation water characteristics:
Temperature
≥50°F (10°C)
CL
-
ΔT IN/OUT
5-15°C
CaCO
3
Max % glycol
50
O
2
43.5-145 PSIg
Pressure
Fe
(3-10 barg)
PH
7.5-9
NO
3
Electrical
10-500 μS/cm
HCO
-
conductivity
3
Langelier
saturation
0-1
H
S
2
index
2-
SO
<50 ppm
CO
4
2
NH
<1 ppm
Al
3
Please note that for special cooling water types such as demineralized,
deionized or distilled it is necessary to contact the manufacturer to ve-
rify which kind of condenser should be used since the standard material
may not be suitable.

3.4 Tips

To prevent damage to the internal parts of the dryer and air compres-
sor, avoid installations where the surrounding air contains solid and/or
gaseous pollutants (e.g. sulphur, ammonia, chlorine and installations in
marine environments).
Th e ducting of extracted air is not recommended for versions with axial
fans.

3.5 Electrical connection

Use approved cable in conformity with the local laws and regulations
(for minimum cable section, see par. 8.3).
Install a diff erential thermal magnetic circuit breaker with contact ope-
ning distance 3 mm ahead of the system (RCCB - IDn = 0.3A) (see the
relevant current local regulations).
Th e nominal current In of the magnetic circuit breaker must be equal to
the FLA with an intervention curve type D.

3.6 Condensate drain connection

Y
Make the connection to the draining system, avoiding connection
in a closed circuit shared by other pressurized discharge lines. Check the
correct fl ow of condensate discharges. Dispose of all the condensate in
conformity with current local environmental regulations.
4

Commissioning

4.1 Preliminary checks

Before commissioning the dryer, make sure:
• installation was carried out according that given in the section 3;
• the air inlet valves are closed and that there is no air fl ow through the
<50 ppm
dryer;
70-150 ppm
• the power supply is correct;
• with Wc version, open the cooling water circuit a few minutes before
<0.1 ppm
starting the dryer.
<0.2 ppm

4.2 Starting

a) Start the dryer before the air compressor;
<2 ppm
b) switch the power on by turning the MAIN SWITCH "
70-300 ppm
"I ON": the POWER LED (2) lights up turning yellow; the crankcase
heater will now start heating .
!
<0.05 ppm
THE CRANKCASE HEATER MUST BE SWITCHED ON 12
HOURS BEFORE STARTING THE DRYER.
<5 ppm
Failure to comply with this rule may cause serious damage to the
compressor.
<0.2 ppm
Once the crankcase is preheated, press the ON button on the control
panel.
x
c) press
: the POWER LED (2) turns green and the compressor
switches on; the dew point is displayed.
Y
Fans (Ac version): if connected with the wrong phase sequence
they turn in the opposite direction, with the risk of being damaged (in
this case the air exits the dryer cabinet from the condenser grilles instead
from the fan grille - see par. 8.6 and 8.7 for correct air fl ow); immediately
invert two phases.
d) Wait 5 minutes, then slowly open the air inlet valve;
e) slowly open the air outlet valve: the dryer is now drying.
Phases Monitor
If appears to display the alarm "CP ", during the start up of the dryer, the
user must verify the wiring of the input terminals of the disconnecting
switch of the dryer.

4.3 Operation

• Leave the dryer on during the entire period the air compressor is wor-
king;
2/6
&
" to

Publicité

Table des Matières
loading

Table des Matières