The battery and/or use cables lead-in is routed through cable bushings. The charger is equipped with 4 output
terminals (M6 threaded rod).
Connect from left to right : -BAT, +BAT D, + BAT1 and BAT2.
The minimal cross-section of the power cable must be at least equal to 3 x 1,5mm².
The minimal cross-section of the power cable must be at least equal to 3 x 2,5mm² in 230 Vac and 3x4mm2 in
115Vac.
The rating of the upstream circuit-breakers should match the equipment's requirements.
The installer should choose the types of cable (H07-VK, MX...) according to the type of application and the
applicable standards.
4.2.2 Precautions regarding electromagnetic disturbance generated by the appliance
Use shielded cables for all the connections (*). The shielding should be earthed at both the transmitting and the
receiving ends.
Keep cable length and shielding connections down to a minimum.
Route cables as close as possible to conductive parts ("loose" cables or loops should be avoided – cables should
be flattened against conductive parts).
Keep power cables separate from battery cables.
Keep power cables separate from control cables (at least 200mm).
The cables should only supply power to this appliance; any branch-offs or short-outs intended to power another
appliance are prohibited.
(*) This is a recommendation for installation rather than an obligation. The installing electrician should decide
whether or not to use shielded cable depending on the EMC environment.
4.2.3 Options
The options are not bundled with standard CPS2 battery chargers; they are available from your reseller.
Only options marketed by Cristec may be mounted with chargers.
The following options are available for the CPS2 range:
Remote On/Off charger control: reference A/M-CPS2
A 5-metre cable + On/Off switch; connect to K8 connector (see drawing in appendix)
Remote Boost control: reference BAD-CPS2
A 5-metre cable + Boost On/Off switch; connect to K11 (see drawing in appendix)
Night function (switches fan off): reference AR-VENT-CPS2
A 5-metre cable + On/Off switch; connect to K9 connector (see drawing in appendix)
ATTENTION: use of this function automatically reduces the output power to allow the fan to be
turned off. It should not be used permanently, otherwise the batteries run the risk of running down and
charger operation may be prematurely affected.
Temperature probe: reference STP-CPS2
Compensates the charging voltage according to temperature
24V Charger: -36mV/°C
A 5-metre cable + probe; connect to K2 (see attached drawing)
Digital display unit: reference SEEL009104
Displays the state of the charger (ON/OFF), the current of the charger, the voltage on each of the 3
outputs
A 10-metre cable + display unit; connect to K3
CPS2OEM24V-40ADEB.DOC
20