3.2.3. Cable linking the earth to the installation
The charger's case should be connected to the installation's earthing system in accordance with current
standards governing the relevant application.
To that effect, connect the installation-to-earth cable to the earthing screw located inside the charger (see
chapter "user interface area").
This cable's cross-section should be at least 2.5mm², type HO7-VK and equipped with an appropriate
terminal.
3.2.4. Precautions regarding electromagnetic disturbance generated by the appliance
Use shielded cables for all the connections (*). The shielding should be earthed at both the transmitting and
the receiving ends.
Keep cable length and shielding connections down to a minimum.
Route cables as close as possible to conductive parts ("loose" cables or loops should be avoided – cables
should be flattened against conductive parts).
Keep power cables separate from battery cables.
Keep power cables separate from control cables (at least 200mm).
The cables should only supply power to this appliance; any branch-off or short-out intended to power
another appliance are prohibited.
(
)
*
This is a recommendation for installation rather than an obligation. The installing electrician should
decide whether or not to use shielded cable depending on the EMC environment.
C
3.2.5.
ABLING PRINCIPLE
3.2.5.1.
Cabling type
3.2.5.2.
Other type of installation
Refer to appendix 3.
3 output charger
(in case of charger setting)
AC input
Engine start-up battery
or less-used battery
Battery connections
(in case of charger setting)
CPS3OEM-3M-DEB
Auxiliary battery BAT1
Auxiliary battery BAT2
Not all the ouputs have to be connected
14-10-09 N°10381 13A
22