Controller parameter
(see Operating Instructions, Bleeding measuring module chapter 4.3 controller
parameter / - 1 bleeding):
limit W+:
limit W-:
switch delay time on:
switch-off delay:
direction of (control) action:
controller module:
limit contact L-:
limit contact L+:
limit contact (X2SD):
limit controller out:
3.2
Biocide metering
High temperatures and high mineral concentration promote the growth of
microbiological cultures in the cooling water. For the protection of the equipment and to
prevent health hazards to humans, it is necessary to add a dose of a germicide product
(biocide) into the cooling water circulation at regular intervals.
With the Multronic, it is possible to trigger a timer-controlled biocide metering via an
optional timer module.
The following settings are to be used in the Timer module (see also Operating
instructions Timer module, chapter 4.1 controller parameter).
• Time:
• Metering time:
• Tracking time:
• Metering relays:
• Pre-circulation:
• Pre-circulation starts:
• Valid:
• Maximum interruption time: 0 to 99 min.
The operating method of the timer is illustrated in chapter
It is important to couple the timer module enable with the desalination module that is to
be controlled through the additional controller enable in the module configuration of the
desalination module (see Operating instructions bleeding module chapter 4.1
Calibration „add. Controller enable" - module 2).
Bleeding is blocked during the metering and residence time.
417101341_Anhang14_Kuehlwasser.doc
Cooling water treatment
upper bleeding value e. g. 1600 µS/cm
lower bleeding value e. g. 1400 µS/cm
0,5 sec
0,5 sec
negativ
on
e. g. 600 µS/cm
e. g. 1800 µS/cm
any, (e. g. 2 %)
no
00:00 to 23:59
1 to 600 min.
0 to 600 min.
first/second or both timer module relays
0 to 99 min.
1 to 99
Mo
Tu
We
- 22 -
Th
Fr
Sa
in the status diagram.
2.2
Su
Rev.: 05-07/10