Early desalination:
Stays in condition if enabled at the timer module and enable at
the controlled desalination module and measured value >
under set point (W-).
The desalination process is initiated manually.
Early desalination cancelled:
Stays in condition if enable signal at the timer module or at the
controlled desalination module is missing.
The desalination controller is turned off (enable: off).
Metering:
Stays in condition if the timer module enable is on and
metering time has not expired.
The desalination controller is disabled.
Metering cancelled:
Stays in condition through missing enable at the timer module.
Metering
is
desalination is also disabled.
Acting:
Stays in condition only because Tracking time has not yet
expired (enable at the timer module is of no consequence!)
The biocide controller is off (no relays switched) and the
desalination controller is disabled.
During the transition from acting to operating, the next biocide metering time is newly
ascertained in dependence on the current time. This can have the result that the times
that would have become active during the last biocide metering are skipped.
NOTE
417101341_Anhang14_Kuehlwasser.doc
cancelled
(biocide
If the desalination controller is disabled, i.e. the biocide metering procedure is in
the process of metering, cancelled metering or in acting, the state of enable at the
desalination module is not important.
Cooling water treatment
controller
is
off)
and
- 20 -
Rev.: 05-07/10