CAUTION
SANICONDENS
®
is a pump for lifting condensate water from
an air conditioning system, a condensation boiler or from
refrigeration units. Include a neutralisation device if necessary
(see the manufacturer's instructions for your boiler).
The pump starts automatically and has a high level of
performance, safety and reliability provided that all the
installation and maintenance instructions described in this
notice are strictly followed.
Please take particular note of the information marked by :
«
» Indication that a risk of electrical origin exists,
«
» Instructions for use only by qualified professionals.
OPERATING PRINCIPLE
SANICONDENS
contains a pump. The tank of the
®
SANICONDENS
®
is fitted with a float which controls the
operation of the motor. When the condensate enters the tank,
the pump starts up.
2
SPARE PARTS: see fig.2
3
DIMENSIONS: see fig.3
4
SANICONDENS
AREA OF APPLICATION AND
®
TECHNICAL DATA
Air conditioning systems, boilers,
Application
Type
Max. vertical pumping
Maximum flow rate (gal / hour)
Min. pH
Voltage
Frequency
Power rating
Current consumption
Electrical class
Protection index
Sound level
Maximum allowable temperature 160° F (70° C)
Net weight
Tank volume
Supply cable
Discharge hose
Alarm cable (3 core)
Wall fastening
CAUTION:
All applications other than those described in this notice are
prohibited.
5
PERFORMANCE CURVES: see fig.5
6
VERTICAL PUMPING/HORIZONTAL PUMPING:
see fig.6
refrigeration units
CD10
15 Ft (4.5 m)
86 (326 l/h)
2.5
110-115 V
60 Hz
60 W
1.5 A
I
IP20
< 45 dBA
S3 15% (1min30 ON, 8min30 OFF)
4.5 lbs
2 liters
6 Ft (2 m)
20 Ft (6 m)
6 Ft (2 m)
Yes
7
INSTALLATION
SANICONDENS
®
may be mounted on a wall by using the
mounting tabs on the tank..
The unit should be easy to access for testing and
maintenance.
The unit must be installed leveled. Adjust the
installation using a level before mounting the unit.
Make sure that the equipment is protected from damp while
installing it.
7b
CONNECTING TO THE DISCHARGE PIPE
The SANICONDENS
®
A
the flexible hose
(supplied : length 20 Ft). This hose should
be used to form the vertical section of the discharge pipe.
• Place the flexible hose onto the non-return valve of the
SANICONDENS
®
(see diagram
• Position the flexible hose in the most vertical position
possible to avoid it kinking.
• It is advisable to make a smooth bend to avoid the hose
from kinking.
• The discharge vinyl tubing (included) can be connected to
a PVC line large in diameter by using the plastic reducer
Y
that is provided with the system.
As shown on the fig.
end of the 3/8" vinyl tubing at the top and it increases the
diameter to ease the connection to a PVC line. (Reducer
is 3/8" barbed x 3/4" male end)
The SANICONDENS
®
prevent re-activation.
ELECTRICAL CONNECTION
1. The electrical installation should be carried out by a qualified
person. The unit should be connected to a fully grounded
electrical supply. The SANICONDENS
single phase AC 60 Hz supply.
7c
CONNECTION AT THE COVER INLET
The unit has 2 inlets 1" in diameter (1 on each side - see fig.
7a
). To connect the water to be drained off, connect the
water inlet to one of the inlets. If necessary, use the adapter
X
(3/4", 1-1/4", 1-1/2" in diameter).
INSTRUCTIONS INTENDED SOLELY FOR
QUALIFIED PROFESSIONALS
7d
ALARM
SANICONDENS
®
is fitted with a detection system
that can trigger an alarm if the water level rises too high
(audible or visual alarm, 1.5V to 120V), see diagram
1
. Brown wire: shared wire
2
. Black wire: normally off
3
. Blue wire: normally on
To fit the alarm, connect the blue and brown wires
of the alarm to the respective terminals on the
SANICONDENS
.
®
4
discharge pipe must be connected to
) .
7b
7f
, the plastic fitting connects to the
is fitted with a non-return valve to
®
requires a 120V
:
7d