TROUBLESHOOTING
Problem
Generator is running, but no AC
output is available.
Generator runs good but bogs
down when loads are connected.
Appliances don't work after utility
power comes back on.
GFCI breaker in generator control
panel trips.
TROUBLESHOOTING
Cause
1.
Generator circuit breaker is
open.
2. Poor connection or defective
cord set.
3. Connected device is bad.
4. Fault in generator.
1.
Short circuit in a connected
load.
2. Generator is overloaded.
1.
Transfer switch in GENERATOR
position.
2. Circuit breaker in main
distribution panel is open.
1.
Ground fault in connected load.
2. Defective GFCI device.
3. Neutral bonded to ground in
transfer switch.
15
Solution
1.
Reset circuit breaker.
2. Check and repair.
3. Select a different appliance or
load that is in good condition.
4. Contact authorized service
center.
1.
Disconnect shorted electrical
load.
2. See "Load Management" on page
13.
1.
Set switch to UTILITY position.
2. Reset circuit breaker in main
distribution panel.
1.
Remove load with fault.
2. Contact authorized service
center.
3. Contact authorized service
center.