TROUBLESHOOTING
Problem
Automatic transfer switch does
not transfer to generator
Automatic transfer switch does
not transfer to utility
Generator is still running after
switch transfers to utility power
Generator is still running after
utility power is restored
Briggs & Stratton Power Products Automatic Transfer Switch
Installation and Owner's Manual
Cause
1.
Generator breaker open.
2.
Generator voltage not acceptable.
1.
Main distribution panel breaker
open.
2.
Utility voltage not acceptable.
Engine cool down period.
1.
Minimum engine run time has not
elapsed.
2.
Fuse(s) in transfer switch is
defective.
Correction
1.
2.
1.
2.
Engine will stop after 1 minute.
1.
2.
11
Reset generator circuit breaker.
Refer to generator manual.
Reset main distribution panel
breaker.
Wait for utility voltage to return to
normal.
Wait five minutes for transfer
switch to retransfer to utility
power.
Check fuse(s) and replace if
necessary.