ELECTRIC CONNECTION
The control unit and the plant must be installed and connected by authorized personnel according to the standards in force.
All operations must be performed with mains power disconnected.
Connect the feeding cable of the switchboard with an electronic bipolar switch respecting at least a 3 mm distance between the contacts.
Power supply 230V~ 50 / 60 Hz, it is necessary to provide for the correct connection to the grounding plant.
WARNINg: The control unit must be connected to the mains with a differential line cut-off switch according to the regulations in force. Correct
operation of the appliance is only guaranteed for pumps and valves approved by La Nordica. La Nordica is not liable for any improper use of
the appliance.
WARNINg: In any case, the power cable has to be replaced by authorised personnel ONLy (entitled by La Nordica): authorised
dealers and/or fitter. ATTENTION: the feeding cable must not be in contact with hot parts - MAX 75 °C.
See Chapter DISPLAY CONNECTION.
FLOW CHART - MENU
LANGUAGE
BUZZER
ON - OFF
SET DEGREES
°C- F
DISPLAY
10 - 100%
TECHNICAL
SETTINGS
SYSTEM
( PR06 = Off )
ITALIANO
ENGLISH
FRANCAIS
ESPANOL
DEUTSH
SETTINGS FACTORY
CODE 44
TEST OUTPUTS
I1= xx°C
(
STATUS Stove
I2= xx°C
I3= xx°C
I4= On / Off
PR06
PRODUCT
CODE 33
PR08 BOILER (On / Off )
PR09 SET BOILER Max
( 47 - 70°C )
PR10 SET BOILER Min
( 30 - 46°C )
PR11 PUFFER ( On / Off
)
PR12 thermal differential to PUFFER On (5 - 12°C) Default = 7°C
PR13 thermal differential to PUFFER Off (3 - 8°C)
ENgLIsH
PR01 CIRCULATOR 1 Threshold OUT 1 (55- 65°C)
PR02 CIRCULATOR 1 Delta OUT 1
TEST OUT 1
TEST OUT 2
PR03 CIRCULATOR 2 Threshold OUT 2 (65 - 75°C)
Default = Heating device 70°C
TEST OUT 3
PR04 CIRCULATOR 2 Delta OUT 2
Heating device
probe)
PR05 ANTIFREEZE Threshold
PUFFER
(
probe)
BOILER
(
probe)
(Flow switch)
0 = Heating device DSA
1 = All Inclusive
2 = WATER CONNECTION KIT
Default = 60°C
Default = 30°C
Default = 5°C
Default = Heating device 60°C
(1 - 5°C)
Default = 5°C
(1 - 5°C) Default = 5°C
(2 - 10°C)
Default = 5°C
35