Technical description
(6)
Tailpipe
(7)
Collar nut
(8)
Flow direction
3.2
Functional description
The presettable thermostatic valve AQH maintains the differential pressure
at a constant value via the presetting cross-section and the regulating
cross-section of the valve. The valve authority amounts to 100% (a=1).
You can set the maximum volume flow with the help of the enclosed preset-
ting key.
For room temperature control, you can screw a thermostat or an actuator
onto the thermostatic valve.
3.3
Technical data
General information
Max. operating temperature t
Min. operating temperature t
Max. operating pressure p
Control range
Fluid
Valve authority
22
+110 °C
s
+2 °C
s
1000 kPa (10 bar)
s
35 - 420 l/h (the set values are visible
from outside; without table)
Water or suitable ethylene/propylene
glycol water mixtures according to VDI
2035 (max. glycol proportion 50 %, ph
value 6.5-10). Not suitable for steam, oily,
polluted and aggressive fluids.
100% (a=1)
During part load operation with
steady control (e.g. in combina-
tion with thermostats for room
temperature control), the valve
authority of the thermostatic
valve AQH amounts to 100 %
(a = 1) within the effective valve
stroke.
Thermostatic valve AQH
118309480-V01.05.2020