ƒ
ƒ
Branch circuit protection (UL Guide No. JHFR2)
Type
E94ASxE1454
E94ASxE1724
E94ASxE2024
E94ASxE2454
E94ASxE2924
E94ASxE3664
E94ASxE4604
E94ASxE5724
E94ASxE6354
E94ASxE6954
Tab. 2-1
100 kA SCCR with above fuses.
ƒ
Ferraz-Schawmut A50QS fuses may be substituted for A50-P fuses.
ƒ
170M fuses from Bussmann shown use -/80 visual indicator. -TN80 Type T, -/110 or
ƒ
TN/110 Type T indicater fuses of the same size and amperage may be substituted.
252
Branch circuit protection:
Suitable for use on a circuit capable of delivering not more than
100000 rms symmetrical amperes, 500 V max., when protected by the
specified fuses ( Tab. 2-1).
Voltage of the fuses must at least be suitable with the input voltage of the
drive.
The integral solid state protection does not provide branch circuit protection
and that branch circuit protection has to be provided externally in
accordance with manufacturers instructions, the National Electrical Code
and any additional codes.
For information on the protection level of the internal overload protection
for a motor load, see the corresponding Application Manuals or Software
Helps.
For information on rating and proper connection of the thermal protector
(only for connection to motors having integral thermal protection), see the
corresponding Application Manuals or Software Helps.
Maximum surrounding air temperature: 55 °C with derating.
Use 75 °C copper wire only, except for control circuits.
Control card protection:
External fuse for 24 Vdc supply voltage of control terminal X2. Rated 4 A DC
fuse UL248-14.
Bussmann
Fuse rating
250 A, 700 V
170M3016
315 A, 700 V
170M3017
350 A, 700 V
170M3018
400 A, 700 V
170M4012
500 A, 700 V
170M4014
630 A, 700 V
170M4016
700 A, 700 V
170M4017
900 A, 700 V
170M6013
900 A, 700 V
170M6013
900 A, 700 V
170M6013
Type
Ferraz-Shawmut
2061032.250
2061032.315
2061032.350
2061032.400
2061032.500
206xx32.600
2061032.700
2063032.900
2063032.900
2063032.900
(Short Circuit Current Rating)
o U
L
R
Alternate type
SIBA
6.6URD30D08A0250
6.6URD30D08A0315
6.6URD30D08A0350
6.6URD30D08A0400
6.6URD30D08A0500
A50-P600
6.6URD31D08A0700
6.6URD33D08A0900
6.6URD33D08A0900
6.6URD33D08A0900