Installation data
Terminals:
DIN/VDE 0609
Screw terminals with wire guards,
for light PVC wiring and
max. 2 × 0.75 mm
Permissible vibrations: 2 g acc. to EN 60 068-2-6
3 × 50 g
Shock:
2 shocks each in 6 directions
acc. to EN 60 068-2-27
Electrical insulation:
All circuits (measuring inputs /
measuring outputs / power supply)
are electrically insulated
Regulations
Housing protection
(acc. to IEC 529
resp. EN 60 529):
IP 40
Terminals IP 20
Electrical standards:
Acc. to IEC 1010 resp. EN 61 010
Test voltage:
Power supply versus:
– all 3.7 kV, 50 Hz,
1 min.
Measuring inputs versus:
– measuring outputs 2.3 kV,
50 Hz, 1 min.
Measuring input 1 versus:
– measuring input 2
2.3 kV, 50 Hz, 1 min.
Measuring output 1 versus:
– measuring output 2
2.3 kV, 50 Hz, 1 min.
Environmental conditions
Commissioning
– 10 to + 55 °C
temperature:
Operating
– 25 to + 55 °C
temperature:
– 40 to + 70 °C
Storage temperature:
Annual mean
≤ 75%
relative humidity:
7. Exchanging frontplates
Apply gentle pressure to the transparent cover as shown in
Fig. 3 until pops out on the opposite side. The label in the
cover can be replaced and used for notes.
After replacing the label in the transparent cover, the trans-
parent cover can be snapped into the front of the device
again. This is done by inserting it behind the edge at the
bottom and pressing it gently down and to the rear with the
finger until it snaps into place (right side of Fig. 3).
or 1 × 2.5 mm
2
2
Fig. 3. Left: Removing the transparent cover
8. Withdrawing and inserting the device
Fig. 4
Insert the withdrawing handles (2) into the openings (9) until
they snap into place. Withdraw the front part together with
the main PCB out of the housing.
To reassemble the unit, insert the front part together with the
main PCB into the housing until the swallow-tailed sections
engage in each other.
9. Mounting
The SINEAX TV 808 can be mounted either on a top-hat rail
or directly onto a wall or mounting plate.
9.1 Top-hat rail mounting
Simply clip the device onto the top-hat rail (EN 50 022) (see
Fig. 5).
ON
ON
(
Right: Inserting the transparent cover.
(9)
(2)
ON
(
(
Make sure that the ambient temperature stays
within the permissible limits:
– 25 and + 55 °C
ON
ON
(
Fig. 5. Mounting on
top-hat rail 35 × 15
or 35 × 7.5 mm.
17