Notes
10.1 Connecting the measuring input leads
Measurement/Application
DC current measurement
DC voltage measurement
10.2 Connecting the measuring output leads
Connect the measuring output leads A1 to terminals 4 (–) and
9 (+), the leads A2 to terminals 3 (–) and 8 (+).
Note: Take care that the amplifier's maximum permissible
external burden R
ext
"6. Technical data").
10.3 Connecting the power supply leads
Connect the power supply leads to terminals 5 (
+
10 (
).
~
A two-pole switch must be included in the supply connection
where facility for switching SINEAX TV 808 off is desired.
Note:
An external supply fuse must be provided for DC
supply voltages > 125 V.
11. Configuration
The SINEAX TV 808 unit has to be opened before it can be
configured (see Section "8. Withdrawing and inserting the
device").
11.1 Standard input ranges
Soldered jumpers are provided for the coarse setting of the
input ranges and the fine adjustment is accomplished using
the potentiometers "Zero" and "Span".
100 must be added to the designations of the soldered
jumpers in the table for channel 1 and 200 for channel 2.
(Example: Input range for input 1 and input 2 = 0...20 mA.
Jumpers 1, 5, 6 and 11 must be inserted for this range.
– The corresponding jumpers for channel 1 are B101, B105,
B106 and B111.
– The corresponding jumpers for channel 2 are B201, B205,
B206 and B211).
Input 1
Input 2
1 (–), 6 (I1+)
2 (–), 7 (I2+)
1 (–), 11 (U1+) 2 (–), 12 (U2+)
is not exceeded (see Section
– ~
) and
Current [mA]
0 ... 0.1
1, 3
0 ... 0.2
1, 3
0 ... 0.5
1, 4
0 ... 1
1, 4
0 ... 2
1, 4
0 ... 5
1, 5
0 ... 10
1, 5
0 ... 20
1, 5
0.2 ... 1
1, 4
1
... 5
1, 4
2
... 10
1, 5
4
... 20
1, 5
– 0.1 ... 0 ... + 0.1
1, 3
– 0.2 ... 0 ... + 0.2
1, 3
– 0.5 ... 0 ... + 0.5
1, 4
– 1
... 0 ... + 1
1, 4
– 2
... 0 ... + 2
1, 4
– 5
... 0 ... + 5
1, 5
– 10
... 0 ... + 10
1, 5
– 20
... 0 ... + 20
1, 5
Voltage [V]
0 ... 0.06
0 ... 0.1
0 ... 0.2
0 ... 0.5
0 ... 1
2
0 ... 2
2
0 ... 5
2
0 ... 10
1
0 ... 20
1
0 ... 40
1
0.2 ... 1
2
1
... 5
2
2
... 10
1
4
... 20
1
– 0.1 ... 0 ... + 0.1
– 0.2 ... 0 ... + 0.2
– 0.5 ... 0 ... + 0.5
2
– 1
... 0 ... + 1
2
– 2
... 0 ... + 2
2
– 5
... 0 ... + 5
1
– 10
... 0 ... + 10
1
– 20
... 0 ... + 20
1
11.2 Standard output ranges
Soldered jumpers are provided for the coarse setting of the
output ranges and the fine adjustment is accomplished using
the potentiometers "Zero" and "Span".
Current
Soldered jumpers Voltage Soldered jumpers
[mA]
Channel Channel [V]
1
2
0 ... 20
B120
B220
4 ... 20
B121
B221
± 20
–––
–––
Soldered jumpers
7, 10, 11
8, 11
9, 10, 11
7, 10, 11
8, 11
6, 7, 8, 10, 11
10, 11
6, 11
8, 10, 11
12, 15
6, 9
12, 15
6, 7, 10, 11
12, 15
6, 7, 8, 11
12, 15
8, 11
13, 14, 16
7, 9
13, 14, 16
7, 10, 11
13, 14, 16
8, 11
13, 14, 16
6, 9
13, 14, 16
10, 11
13, 14, 16
6, 11
13, 14, 16
6, 7
13, 14, 16
Soldered jumpers
6, 9, 10, 11
7, 8, 10, 11
6, 8, 9, 11
6, 7, 8, 9, 10
6, 7, 8,10, 11
7, 8, 9, 11
8, 10
10, 11
6, 11
8
9, 10, 11
12, 15
6, 8, 9, 10
12, 15
6, 7, 10, 11
12, 15
6, 7, 8, 11
12, 15
6, 8, 9, 11
13, 14, 16
6, 7, 9, 10
13, 14, 16
7, 8, 10, 11
13, 14, 16
7, 8, 9, 11
13, 14, 16
6, 8, 9, 10
13, 14, 16
10, 11
13, 14, 16
6, 11
13, 14, 16
8
13, 14, 16
Channel Channel
1
2
B120
B220
0 ... 10 B122
B222
B123
B223
B121
B221
2 ... 10 B122
B222
B123
B223
B122
B222
± 10
B123
B223
19