Shock:
3 × 50 g
2 shocks each in 6 directions acc.
to EN 60 068-2-27
Electrical insulation:
All circuits (measuring input/meas-
uring output/power supply) are
electrically insulated
Regulations
Housing protection
(acc. to IEC 529 resp.
EN 60 529):
IP 40
Terminals IP 20
Safe insulation:
Acc. to IEC 1010 and DIN/VDE 106,
part 101
Test voltage:
Measuring input versus:
– measuring output 2.3 kV, 50 Hz,
1 min.
– power supply 3.7 kV, 50 Hz,
1 min.
Measuring output versus:
– power supply 3.7 kV, 50 Hz,
1 min.
Environmental conditions
Climatic rating:
Climate class 3Z acc. to
VDI/VDE 3540
Commissioning
temperature:
– 10 to + 55 °C
Operating temperature: – 25 to + 55 °C, Ex – 20 to + 55 °C
Storage temperature:
– 40 to + 70 °C
Annual mean
relative humidity:
≤ 75%
7. Exchanging frontplates
Apply gentle pressure to the transparent cover as shown in
Fig. 3 until pops out on the opposite side. The label in the
cover can be replaced and used for notes.
After replacing the label in the transparent cover, the trans-
parent cover can be snapped into the front of the device
again. This is done by inserting it behind the edge at the
bottom and pressing it gently down and to the rear with the
finger until it snaps into place (right side of Fig. 3).
ON
ON
(
Fig. 3. Left: Removing the transparent cover
Right: Inserting the transparent cover.
16
8. Mounting
The SINEAX TV 808 can be mounted either on a top-hat rail
or directly onto a wall or mounting plate.
Make sure that the ambient temperature stays
within the permissible limits:
– 25 and + 55 °C for standard instruments
– 20 and + 55 °C for instruments in Ex-version!
8.1 Top-hat rail mounting
Simply clip the device onto the top-hat rail (EN 50 022) (see
Fig. 4).
8.2 Wall mounting
While pressing the latch (4) in the base of the device (Fig. 5,
left) pull out the isolating amplifier securing brackets (1). To
return the brackets to their original positions, the latch (5) in
the base of the vice has to be depressed before applying
pressure to the securing brackets (1) (see Fig. 5, right).
(1)
(2)
(3)
(2)
(4)
(1)
Drill 2 holes in the wall or panel as shown in the drilling pattern
(Fig. 6). Now secure the power pack to the wall or panel using
two 4 mm diameter screws.
ON
ON
(
Fig. 6. Drilling pattern.
Fig. 4. Mounting on
top-hat rail 35 × 15 or
35 × 7.5 mm.
(1)
Fig. 5. Rear of device.
(1) Screw hole brackets
(2) Top-hat rail clip
(3) Rubber buffers
(4) Latch for pulling the
screw hole brackets
out
(5) Latch for pushing
the screw hole
brackets in
(5)