11.3 Specific user output ranges
Units that have been configured for a specific user output range
cannot be subsequently reconfigured.
Span 2
Zero 2
Span 1
Zero 1
Fig. 8. Position of the soldered jumpers B..., potentiometer "Zero"
and "Span".
12. Commissioning
Switch on the measuring inputs and the power supply. The
green LED lights continuously after switching on.
The power supply unit must be capable of supplying
a brief current surge when switching on. The
instruments presents a low impedance at the in-
stant of switching which requires a current I
≥ 160 mA for the version with a power
... I
start
supply range of
24 – 60 V DC/AC
or
≥ 35 mA for the version with a power supply
... I
start
range of
85 – 230 V DC/AC
13. Maintenance
No maintenance is required.
20
14. Releasing the isolating amplifier
Release the isolating amplifier from a top-hat rail as shown in
Fig. 9.