Control characteristic
Control characteristic for factory pre-setting of 58 °C
Between 53 °C and set-
point 58 °C, the throttling
positions are set as a func-
tion of temperature.
Maximum throttling posi-
tion between set-point 58
°C and 63 °C with min.
volume flow.
© www.kemper-olpe.de – 03.2021 / K410014100002-00 – 11 / 32
Valve opens at > 63 °C up
to a constant throttling
position at disinfection
temperature of 70 °C.