Load Connection With Vibration Alert; External Conductor Test (Phase); Phase Sequence Test; Technical Data - Gossen MetraWatt DUSPOL analog 1000 Mode D'emploi

Masquer les pouces Voir aussi pour DUSPOL analog 1000:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 7
parts to be tested.
-
The level of voltage applied is indicated by means of the
LED step indicator
-
Actuate both push-buttons
level indicator
load in the voltage tester.
-
Alternating voltages (AC) are indicated by the +24 V LED
and the -24 V LED lighting up simultaneously.
-
Direct voltages (DC) are indicated by the +24 V LED or the
-24 V LED lighting up. The polarity indication J shows the
polarity (+ or -) applied to the probe tip L2/+
-
To differentiate between low-energy and high-energy volt-
ages (e.g. capacitively induced interference voltages), an
internal load in the voltage tester can be connected by ac-
tuating both push-buttons (see section 5).
5.
Load connection with vibration alert (figure A/B)
Both handles L1
5
. Actuate both push-buttons to switch to a lower internal re-
sistance. Here, voltage is applied to a vibration motor (motor
with unbalanced mass). From approx. 200 V on, this motor is
set in rotary motion. With the voltage increasing, the motor's
speed and vibration increases as well. The duration of the test
with a lower internal resistance (load test) depends on the level
of voltage to be measured. In order to avoid an inadmissible
warming of the device, it is provided with a thermal protection
(controlled reduction). With this controlled reduction, the speed
of the vibration motor is reduced and the internal resistance
increases.
The load connection (with both push-buttons being actuated)
can be used ...
-
to suppress reactive voltages (inductive and capacitive
voltages),
-
to charge capacitors,
-
to trip 10/30 mA FI safety switches. The tripping of the FI
safety switch is done by testing the external conductor
(phase) to PE (earth). (figure D)
6.
External conductor test (phase) (figure C)
-
Fully grasp the handles L1
sure a capacitive coupling to earth.
-
Apply the probe tip L2/+
During the single-pole external conductor test (phase),
make absolutely sure not to touch the probe tip L1/-
and that it remains contactless.
-
If an "R" symbol is shown on the LC display
nal conductor (phase) of an AC voltage is applied to this
system part.
Note:
The single-pole external conductor test (phase) can be carried
out in an earthed mains from 230 V, 50/60 Hz (phase to earth)
on. Protective clothing and insulating conditions on site might
impair the function.
Attention!
The absence of voltage can only be determined by means of
a two-pole test.
7. Phase sequence test (figure E/F)
-
Fully grasp both handles L1
sure a capacitive coupling to earth.
-
Apply the probe tips L1/-
ductors (phases) of a three-phase mains and check whether
the external conductor voltage of e.g. 400 V is applied.
-
A clockwise phase sequence (phase L1 before phase L2)
is given, if an "R" symbol is shown on the LC display
Nothing is shown on the LC display, if no clockwise phase
sequence has been detected.
-
The phase sequence test always requires a countercheck!
If the LC display shows the clockwise phase sequence by
means of the "R" symbol, the LC display must show noth-
ing during the countercheck with the probe tips L1/-
and L2/+
If the LC display shows the "R" symbol in both cases, the
earthing is too weak.
Note:
The phase sequence test can be carried out in an earthed
three-phase mains from 230 V, 50 / 60 Hz (phase to phase)
on. Protective clothing and insulating conditions on site might
impair the function.
8.

Technical data

-
regulation: DIN EN 61243-3: 2011, IEC 61243-3: 2009
-
nominal voltage range: 12 V to 1,000 V AC/DC
-
nominal frequency range f: 0 to 60 Hz
-
max. indication error: U
- internal resistance of measuring circuit: 180 kΩ,
-
current consumption of measuring circuit: I
(1,000 V)
-
current consumption of load circuit: I
-
polarity indication: + 24 V LED, - 24 V LED, + 12 V LED, -
12 V LED (with push-buttons being actuated)
-
external conductor (phase) test and phase sequence test:
≥ U
230 V, 50/ 60 Hz
n
- vibration motor, start: ≥ U
overvoltage category: CAT IV 600 V,  CAT III 1,000 V
-
-
protection category: IP 65 (DIN VDE 0470-1 IEC/ EN
60529)
6 - first index: protection against access to dangerous
parts and protection against solid impurities, dustproof
5 - second index: protected against water jets. The device
can also be used in the rain.
-
max. allowable Duty cycle: 30 s (max. 30 seconds), 600 s off
-
weight: approx. 250g
-
length of connecting cable: approx. 1,000 mm
-
operating temperature and storage temperature range:
- 20 °C to + 45 °C (climatic category N)
-
relative air humidity: 20 % to 96 % (climatic category N)
-
times of controlled reduction (thermal protection):
03/2013
8
4
, the 12 V LED step (+/ -) and an internal
6
and L2
3
being inverted.
DUSPOL
.
5
to connect the plunger coil
7
are equipped with push-buttons
6
and L2
3
to the system part to be tested.
6
and L2
2
and L2/+
±15%, ELV U
n
200 V
n
analog 1000
®
3
.
7
, in order to en-
9
, the exter-
7
, in order to en-
3
to two external con-
+0% -15%
n
< 6,0 mA
s
< 550 mA (1,000 V)
s
2
9
.
2
6

Publicité

Chapitres

Table des Matières
loading

Table des Matières