The pilot pressure of the pneumatic controller is dependent on the pressure of the flow
NOTE
of medium: it must not exceed a maximum of 7 bar!
ATTENTION!
Observe the permissible pressure range given on the rating
plate!
Pressure difference between Ports 1 and 3/5 ≥ ≥ ≥ ≥ ≥ 2,5 bar

Electrical connections

Flying lead
connection
Figure: Connection variants for the pilot valve 6104
Pilot valve type 6104
• read the voltage, electrical power, type of protection and current from the rating plate!
• voltage tolerance ±10%
• with 100 % duty cycle and the max. ambient temperature, the coil heats up:
in a single valve assembly, up to approx. 105° C
in a block assembly to approx. 120° C
NOTE
Ensure a long service life for the pilot valve by using a 5µ filtration
ATTENTION!
Note the voltage used! With alternating current, always connect a rectifier into the
circuit!
Round plug
connection M8
T
D
ECHNICAL
ESCRIPTION
Square plug
connection
6510/6511 - 9