Smart-RTC
4.5

Start-up

NOTE
To start proper communication between the heat pump manager and the
Smart-RTC, the heat pump manager and the Smart-RTC must both be
restarted once by switching off their voltage supplies.
NOTE
If 'Cn' appears on the Smart-RTC display, communication to the heat
pump manager has been interrupted. In this case, please check the wiring
and settings, and restart the devices if necessary.
ATTENTION!
If communication cannot be established, the address set on the Smart-
RTC must be checked. WPM software version L03 requires Address 1;
from version L04 Address 50 must be set on the Smart-RTC.
Press the "Rapid heating" and "Key lock" buttons simultaneously
for approximately 3 seconds to check the address. "Code" is
displayed. Turn the rotary pushbutton to change the value and
press the button to confirm the new value. First the value "22"
must be selected and confirmed. Following this, the required
address must be set and confirmed using the rotary pushbutton
on the screen displaying "Addr". Finally, use the rotary
pushbutton to select the screen displaying "ESC" and confirm to
leave the menu.
The Smart-RTC function must be activated on the heat pump
manager. In the menu for technicians, the regulation must be set
Recommended settings for room set
temperature 22°C
Panel heating (35/28 °C)
(floor, wall, ceiling)
Low-temperature radiators (45/38 °C)
Radiators (55/45 °C)
To achieve optimum regulation, select as small a controlling
range as possible between the minimum and maximum return
temperature. Automatic operating mode switching makes it

Elimination of faults:

Building too hot
Building is not heating up
Reference room is hot,
but individual rooms (e.g. bathroom) too cold
Reference room is not
reaching the room set temperature,
but individual rooms (e.g. bathroom) are hot
Start-up must be performed in accordance with the installation
and operating instructions of the heat pump manager.
EN-6
to room temperature (Settings - Heating circuit 1 - Room
temperature regulation) and the temperature sensor must then
be set to Smart-RTC (Settings - Heating circuit 1 - Temperature
sensor).
The greater the deviation between the actual room temperature
and the room set temperature, the faster the return set
temperature is adjusted. The response time can be changed by
means of the adjustable interval value (I value) if required. The
longer the response time, the slower the room set temperature is
adjusted.
Prerequisites:
Deactivation of individual room control, if present, in the
reference room (e.g. room regulation with control via control
valve)
Entry of a minimum return set temperature to prevent the
building from cooling down if there is internal heat recovery
in the reference room.
Entry of a maximum return set temperature to prevent the
building from overheating (e.g. if the windows are open)
Constant room set temperature with the elimination of as
many raising and lowering operations as possible
HINWEIS
Activating the room temperature regulation or changing the room set
temperature can initially result in the room temperature being exceeded.
Minimum return temperature
22 °C
25 °C
30 °C
possible to set an external temperature above which heating
operation is blocked.
Measure 1
Reduce room set temperature
Raise room set temperature,
increase volume flow
Carry out hydraulic equalisation (reduce
volume flow in the reference room)
Carry out hydraulic equalisation (raise
volume flow in the reference room)
452114.66.73 · FD 9408
Maximum return temperature
30 °C
40 °C
50 °C
Measure 2
Reduce minimum return temperature
Raise maximum return temperature
Raise minimum return temperature.
This can lead to the room set temperature in
the reference room being periodically
overshot.
Raise maximum return temperature