BTL7-A/C/E/G _ _ _ -M _ _ _ _ -A/B/CD/Y/Z(8)-NEX-S32/KA _ _
Micropulse Transducer - Rod Style
4
Installation and connection (continued)
Supporting rod made of non-magnetizable material
Fig. 4-9:
Example 2, transducer installed with supporting rod
4.4.1
Connector S32/cable connection KA_ _
Pin
Cable color
-A_10
1
YE yellow
Not used
2
GY gray
3
PK pink
10...0 V
4
RD red
5
GN green
0...10 V
8
WH white
6
BU blue
7
BN brown
Unassigned leads can be connected to the GND on the controller side but not to the shield.
1)
Reference potential for supply voltage and EMC-GND.
2)
Tab. 4-2:
Connection assignment BTL7...-S32/KA_ _
4.5
Shielding and cable routing
Defined ground!
The transducer and the control cabinet must be
at the same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
–
Connect the transducer and controller using a shielded
cable.
Shielding: Copper filament braided, at least 85%
coverage.
–
Connector version: Shield is internally connected to
connector housing.
–
Cable version: On the transducer side, the cable
shielding is connected to the housing.
Ground the cable shielding on the controller side
(connect with the protective earth conductor).
www.balluff.com
Magnet
(e.g. BTL-P-1028-15R)
-G_10
-C_00
-C_70
0...20 mA
20...0 mA
1)
0 V
10...–10 V
La (programming input)
–10...10 V
Lb (programming input)
BTL7-_1_ _-...
GND
2)
20...28 V
4.4
Electrical connection
Depending on the model, the electrical connection is made
using a cable (BTL7...-KA) or a connector (BTL7...-S32).
The connection or pin assignments for the respective
version can be found in Table 4-2.
Note the information on shielding and cable
routing.
-E_00
-E_70
4...20 mA
20...4 mA
Not used
1)
Not used
1)
BTL7-_5_ _-...
GND
2)
10...30 V
Magnetic fields
The position measuring system is a magnetostrictive
system. It is important to maintain adequate distance
between the transducer cylinder and strong, external
magnetic fields.
Cable routing
Do not route the cable between the transducer, controller,
and power supply near high voltage cables (inductive stray
noise is possible). The cable must be routed tension-free.
Bending radius for fixed cable
The bending radius for a fixed cable must be at least five
times the cable diameter.
Cable length
BTL7-A/G
Max. 30 m
BTL7-C/E
Max. 100 m
Tab. 4-3:
Cable lengths BTL7
Prerequisite: Construction, shielding and routing preclude the effect of any
1)
external noise fields.
Ignition protection
"nA" and "tb"
Fig. 4-10: Pin assignment of S32 (view
of connector pins of
transducer), 8-pin M16
circular plug
1)
1)
english
13