BTL7-S5 _ _ (B)-M _ _ _ _ -A/B/CD/Y/Z(8)-NEX-S32/KA _ _
Micropulse Transducer - Rod Style
4
Installation and connection (continued)
Supporting rod made of non-magnetizable material
Fig. 4-9:
Example 2, transducer installed with supporting rod
4.4
Electrical connection
Depending on the model, the electrical connection is made
using a cable (BTL7-...-KA) or a connector
(BTL7- ...-S32).
The connection or pin assignments for the respective
version can be found in Tab. 4-2.
Note the information on shielding and cable
routing.
4.4.1
Connector S32/cable connection KA_ _
BTL7 Standard BTL7 USB-
Pin
Wire
...-S5_ _-...
color
...-S5_ _B-...
1
YE yellow
+Clk
2
GY gray
+Data
3
PK pink
–Clk
4
RD red
Not used
5
GN green
–Data
6
BU blue
GND
7
BN brown
10...30 V
8
WH white
Not used
1) Unassigned leads can be connected to the GND on the controller side
but not to the shield.
2) Communication line
Tab. 4-2:
Connection assignment BTL7...-S32/KA_ _
Fig. 4-10: Pin assignment of S32 (view of connector pins of
transducer), 8-pin M16 circular plug
Clk, Data and supply are stranded in pairs
(see Fig. 4-11).
www.balluff.com
Magnet
(e.g. BTL-P-1028-15R)
Configurable
...-S510-...
...-S510B-...
+Clk
+Data
–Clk
1)
La
2)
–Data
GND
10...30 V
1)
Lb
2)
+Clk
–Clk
+Data
–Data
GND
+24 V
Fig. 4-11:
Connection example for BTL7-S...-KA_ _ 24 V DC with
evaluation/controller
4.5
Shielding and cable routing
Defined ground!
The transducer and the control cabinet must be
at the same ground potential.
Shielding
To ensure electromagnetic compatibility (EMC), observe
the following:
–
Connect transducer and controller using a shielded
cable.
Shield: Braided copper shield with minimum 85%
coverage.
–
Connector version: Shield is internally connected to
connector housing.
–
Cable version: On the transducer side, the cable
shielding is connected to the housing.
Ground the cable shielding on the controller side
(connect with the protective earth conductor).
Magnetic fields
The position measuring system is a magnetostrictive
system. It is important to maintain adequate distance
between the transducer cylinder and strong, external
magnetic fields.
Cable routing
Do not route the cable between the transducer, controller,
and power supply near high voltage cables (inductive stray
noise is possible).
The cable must be routed tension-free.
Bending radius for fixed cable
The bending radius for a fixed cable must be at least five
times the cable diameter.
Cable length
BTL7-S...
Max. 500 m
1) Prerequisite: Construction, shielding and routing preclude the effect of
any external noise fields. Required cable cross-section ≥ 0.6 mm
≤ AWG19.
Tab. 4-3:
Cable length BTL7
For notes on cable length, see Technical data
on page 21, Fig. 8-2.
Ignition protection
"ec" and "tb"
YE
PK
GY
GN
BU
Evaluation
BN
or
controller
1)
or
2
english
13