Cyclical Data Exchange; Inputs (From Mp55Ibs To The Plc) - HBM MP60DP Manuel D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

16
The configuration telegram thus has the following format:
CFG byte
Meaning
1
header
2
length of outputs
3
length of inputs
user−specific data
p
4
5
Tab 6.4:
Contents of the configuration telegram
When using the 32 bit formats data consistency must always be set.

6.3 Cyclical data exchange

Depending on the configuration, the following data content is exchanged:

6.3.1 Inputs (from MP55IBS to the PLC)

Measured values
Measured values can be communicated in various forms of representation.
The forms of representation available for selection are floating (2 words, 32
bit), 16 bit fixed point number (1 word, 16 bit integer in two's complement,
decimal place must be known to the reader) or 32 bit fixed point number (2
words, 32 bit integer in two's complement, decimal place must be known to
the reader). For conversion of the values to fixed point representation the
number of decimal places in the module parameter assignment (display,
CAN−bus) is used as a basis.
HBM
Permitted values for CFG (hex.)
0xC2 (inputs and outputs, 2 bytes manufacturer−specific
0x40 − 0x48 (1 to 9 words of outputs) or
0xC0 − 0xC8 (1 to 9 words of outputs with consistency)
0xC0 − 0xCC or
0x40 − 0x7C (1 to 13 words of inputs with/without
Input data
Output data
PME−MP60DP
data)
consistency)
selection of the data content (see
Tab 6.3)
T b
)
(
A0623-6.1 en/de/fr