Access To Adjustment Mode - elco VL 04.540 DP Notice D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Start-up
Access to the adjustment
Menu "PARAMETER"
Programming of supplementary functions
Access to the setting mode is only
possible when the burner is stopped
(display: "UNIT DEPROGRAMMED" or
"THERMOSTATIC CUT-OFF".) For this
purpose, reduce the temperature at the
boiler controller or remove bridge plug 7.
To activate the setting mode, it is also
possible to enter an access code.
UNIT CONFIGURATION
Code 0
?
PROGRAM
PARAMETER
?
E-BUS ADDRESS
03H
?
POSTVENTIL. (0-240 secs.)
000s
NEXT
?
END STOP (0-100 min)
000 min
NEXT
IMPULS. (1-255 l/m3)
200
NEXT
34
Precautions:
The setting mode is activated via the
access code and the burner setting
must only be adjusted by a technician
adequately qualified and authorised
to handle the MPA 22. The access
code is located on an information
plate affixed to the MPA22 safety unit.
Access to the setting mode:
• Press and hold button
.
• Enter the access code numbers with buttons
• Confirm each number with
SETTING
• If a number is entered incorrectly, button
After entering the correct code, three menus will appear for selection.
"PARAMETER":
"PROGRAM":
"SETTINGS":
"PARAMETER"
The "PARAMETER" menu item is accessed via the setting mode. It allows the
various additional functions and function parameters to be set.
- E-bus address: 03H: Standard address (factory setting). This parameter is required
to establish communication with a PC.
Other addresses are possible: F3H, 73H, 33H, 13H.
Access to the next parameter: Confirm "NEXT" with button
- This parameter enables a postventilation time to be set.
Setting range: 0 s. (= no postventilation) up to 240 s.
PREVIOUS
- This parameter enables a waiting time between a standard disconnection and a
new burner start to be set.
PREVIOUS
Setting range: 0 min. (= no waiting time) up to 100 min.
- This parameter indicates the number of pulses that the gas counter sends to the
control unit for 1 m3 of gas consumed.
PREVIOUS
Setting range: 1 (1 pulse = 1m
07/2009 - Art. Nr. 4200 1023 3700A
During the setting procedure, a time-out
of 30 minutes will be activated if no
buttons are pressed. This time may be
reset by pressing the keypad. After this
time has expired, the boiler stops so that
it cannot run until the setting procedure
is completed. In setting mode, all safety
functions are activated. Flame failure, air
pressure switch failure or a fault in the
stepper motor control will lead to a fault
or safety disconnection.
and after 0.5 seconds, press button
.
allows you to return to the level above.
for programming of additional functions.
for pre-setting the burner during initial start up
for partial programming, for example after thermostatic cut-off
during adjustment or during subsequent correction of the
adjustment values.
3
) to 255 ( 255 pulse = 1m
or
.
.
3
).