Burner Setting Data - elco VL 04.540 DP Notice D'emploi

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Start-up

Burner setting data

Burner power
Mini
Medi.
Maxi
Model
kW
kW
kW
166
230
310
225
350
450
VL 04.540
DP
166
320
500
200
410
540
The above setting data are basic adjustments. The factory setting data are framed in bold. Under normal circumstances, the
setting will enable the burner to operate. In any event, carefully check the setting values. Corrections may be necessary
depending on the characteristics of your installation.
Nozzles
Fuel oil flow
Mini
Medi.
Maxi
45°B
Gph
kg/h
kg/h
kg/h
3,75 +
14
20
26
2,00
5,00 +
19
30
36
2,50
3,75 +
14
27
38
3,75
4,50 +
18
36
47
4,50
07/2009 - Art. Nr. 4200 1023 3700A
Pump pressure
Dimen-
sion
Mini
Medi.
Maxi
Flap
Y
positi.
ignition
mm
bar
bar
bar
P0 (°)
11
11
18
15
14,5
12
12
20
20
22
11
11
22
30
14,5
11
11
22
40
19
Air flap opening
Flap
Valve
Flap
Valve
Flap
positi.
positi.
positi.
positi.
positi.
mini
Medi.
medi.
maxi
maxi
P1 (°)
P2 (°)
P3 (°)
P4 (°)
P9 (°)
16
22
28
40
25
30
40
50
16
22
35
45
23
30
40
50
45
55
60
en
60
31