Initial Start-Up; Configuration Data Air Adjustment - elco P2.190 L/TEH Notice D'emploi

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Initial start-up

Configuration data
Air adjustment
Burner power
kW
Burner
74
130
P2.190 L(SV)
169
124
P2.300 L(SV)
199
241
Bold : Delivery setting; 1kg fuel-oil at 10°C = 11.86kWh
The above adjustments are basic
adjustments. With these settings,
normally, the burner can be started up.
The adjustment must then be verified
using a combustion analyser.
A
B
A
B
58
Nozzle
Fuel-oil flow
60°B/W
kg/h
Gph (Danfoss)
1,75
6,2
2,50
11,0
3,75
14,3
2,50
10,4
4,00
16,8
5,00
20,3
It may be necessary to perform
corrections subject to the single plant.
Favourable combustion values can be
obtained using the
following nozzles:
Air adjustment (A).
Intervene on screw A in the picture:
• turning it anti-clockwise increases
the flow rate;
• turning it clockwise decreases the
flow rate.
Note: screw B not used.
Adjusting the combustion head (B).
Intervene on the screw shown in the
picture:
turn it using a hex spanner until it
reaches the desired value
(index from 0 to 5).
06/2014 - Art. Nr. 4200 1057 7300
Pump pressure
Firing head setting
bar
mm
8
12
1,0
11
3,0
12
12
11
Air flap position
0
1,5
2
4
0
1,8
2
3
5
4
DANFOSS H÷S 80°÷60°
DELAVAN W 60°
STEINEN S 60°

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

P2.240 l/tehP2.300 l/teh