OPTIONAL:
if you connect the brown and black wires to the
control relays on your boiler, it will be switched off if the water
level rises too high in the unit.
ATTENTION:
The maximum current admissible for our detection
system is 0.5A.
To protect the electrical components in the SANICONDENS
once the alarm has been triggered, any water continuing to fill
the tank comes out through the overflow outlets in the cover.
7e
BEFORE TURNING THE DEVICE ON, MAKE SURE YOU
REMOVE THE PROTECTIVE LOCKING PIN FROM THE
REAR OF THE DEVICE
7f
EXAMPLE OF AN INSTALLATION OF
A SANICONDENS
BEST: see fig.
®
8
STANDARDS
This model is eligible to bear the CSA mark shown with
adjacent indicators "C" and "US". The "C" and "US"
indicators adjacent to the CSA mark signify that the product
has been tested according to the applicable CSA (CDN)
and ANSI/UL standards for use in Canada and the USA.
This includes products eligible bear the designation NTRL.
NTRL (Nationally Recognized Testing Laboratory) is a desi-
gnation awarded by the American Occupational Safety and
Health Administration (OSHA) to laboratories authorized to
award the certification according to American standards.
INSTRUCTIONS INTENDED SOLELY FOR
QUALIFIED PROFESSIONALS
9
DISASSEMBLY
If a breakdown occurs, any service on the unit should be carried
out by a qualified technician. In particular the
replacement of the power cable.
Disconnect the electrical supply before carrying out work
on the unit.
BEST
®
7f
10
TROUBLESHOOTING
INSTRUCTIONS RESERVED SOLELY FOR
QUALIFIED PROFESSIONALS
Disconnect the electrical supply before carrying out any work.
FAULT DETECTED
PROBABLE CAUSES
• The pump is not
• The pump does not start
connected to the power supply
• The locking pin has not been
removed.
• The unit is not level.
• Power cut
• Float blocked
• Condensates inlet pipe blocked
• Neutralisation drawer is blocked
• Non-return valve blocked
• The pump does not lift
• Discharge pipe blocked
11
LIMITED WARRANTY
This SFA appliance bears a 3 year warranty starting from
the date of purchase, subject to proper installation and use,
in compliance set out in this notice.
Warranty issues will be handled by the Technical Department
and will be subject to correct installation and usage.
If a replacement is to be issued, this will be only extended
to the first 180 days starting from the date of purchase
and will need to be approved by one of our company's
representative. Warranty repairs will apply after such date
up to the warranty's date of conclusion.
Plumber's invoices for any type of repair, disconnection and
reconnection are not covered by the warranty and are the
end user's responsibility. In no event shall the company be
liable for any special, incidental or consequential damage,
loss or injury of whatsoever nature or kind arising from or in
connection with the product or any component thereof.
ACTION NEEDED
• Plug in the unit.
• Remove the locking pin.
• Please check the unit with a
spirit level.
• Check the mains voltage.
• Clean the SANICONDENS
®
tank.
• Clean the SANICONDENS
®
inlet pipe.
Clean the drawer, replace the
pellets
• Clean the valve.
• Clean the discharge pipe.