CAUTION
SANICONDENS
BEST is a pump for lifting condensate water from
®
an air conditioning system, a condensation boiler or from refrige -
ration units.
The pump starts automatically and has a high level of
performance, safety and reliability provided that all the
installation and maintenance instructions described in this notice
are strictly followed.
Please take particular note of the information marked by :
«
» Indication that a risk of electrical origin exists,
«
» Instructions for use only by qualified professionals.
OPERATING PRINCIPLE
SANICONDENS
BEST contains a pump. The tank of the
®
SANICONDENS
BEST is fitted with a float which controls the
®
operation of the motor. When the condensate enters the tank, the
pump starts up.
The unit has its own neutralization system that can be used to
increase the pH of the acid water from the condensing boiler
2
SPARE PARTS: see fig.2
3
DIMENSIONS: see fig.3
4
SANICONDENS BEST
TECHNICAL DATA
Air conditioning systems, boilers,
Application
refrigeration units
Type
Max. vertical pumping
Maximum flow rate (gal / hour)
Min. pH
Voltage
Frequency
Power rating
Current consumption
Electrical class
Protection index
Sound level
Maximum allowable temperature
Net weight
Tank volume
Supply cable
Discharge hose
Alarm cable (3 core)
Wall fastening
CAUTION:
All applications other than those described in this notice are pro -
hibited.
5
PERFORMANCE CURVES: see fig.5
6
VERTICAL PUMPING/HORIZONTAL PUMPING:
see fig.6
AREA OF APPLICATION AND
®
condens best
15 Ft (4.5 m)
86 (326 l/h)
2.5
110-115 V
60 Hz
60 W
1.2 A
I
IP20
< 45 dBA
160° F (70° C)
S3 15% (1min30 ON, 8min30 OFF)
8 lbs
2 liters
6 Ft (2 m)
20 Ft (6 m)
6 Ft (2 m)
Yes
7
INSTALLATION
SANICONDENS
BEST may be mounted on a wall by using the
®
mounting tabs on the tank..
The unit should be easy to access for testing and
maintenance.
The unit must be installed leveled. Adjust the
installation using a level before mounting the unit.
Make sure that the equipment is protected from damp while
installing it.
7a
Mount the handle
E
using the 2 screws F. Add the contents of
the bag of neutralizing pellets
7b
CONNECTION AT THE COVER INLET
The unit has 4 inlets 1" in diameter (2 on each side - see fig.
To connect the water to be drained off, connect the water inlet to
one of the inlets and close off any unused inlets with the plug D.
If necessary, use the adapter
7c
CONNECTING TO THE DISCHARGE HOSE
The SANICONDENS
BEST discharge pipe must be connected to the
®
flexible hose
A
(supplied : length 20 Ft). This hose should be used
to form the vertical section of the discharge pipe.
• Place the flexible hose onto the non-return valve of the
SANICONDENS
BEST(see diagram
®
• Position the flexible hose in the most vertical position
possible to avoid it kinking.
• It is advisable to make a smooth bend to avoid the hose from
kinking.
• The discharge vinyl tubing (included) can be connected to a
PVC line large in diameter by using the plastic reducer
is provided with the system.
As shown on the fig.
end of the 3/8" vinyl tubing at the top and it increases the
diameter to ease the connection to a PVC line. (Reducer is
3/8" barbed x 3/4» male end)
The SANICONDENS
BEST is fitted with a non-return valve to
®
prevent re-activation.
ELECTRICAL CONNECTION
1. The electrical installation should be carried out by a qualified per -
son. The unit should be connected to a fully grounded electrical
supply. The SANICONDENS
60 Hz supply.
INSTRUCTIONS INTENDED SOLELY FOR
QUALIFIED PROFESSIONALS
7e
ALARM
SANICONDENS
BEST is fitted with a detection system
®
that can trigger an alarm if the water level rises too high
(audible or visual alarm, 1.5V to 120V), see diagram
1
. Brown wire: shared wire
2
. Black wire: normally off
3
. Blue wire: normally on
4
To fit the alarm, connect the blue and brown wires
of the alarm to the respective terminals on the
SANICONDENS
BEST.
®
G
into the drawer
(3/4", 1-1/4", 1-1/2" in diameter).
X
) .
7c
7f
, the plastic fitting connects to the
BEST requires a 120V single phase AC
®
7b
).
Y
that
7e
: