5.3 Adjustments
TRIMMER/DIP SWITCHES ADJUSTMENT ENABLING PROCEDURE
The trimmers and DIPs affect the force limiting safety function. They must be set as instructed, (if not, the modifications will not be accepted and
the RED and GREEN LEDs will flash):
• During the setting phase, the operator stops and it is not possible to carry out commands.
• Press the button
for 4 s (RED and GREEN LEDs on);
• Adjust the trimmers and DIP switches within the 5-minute time limit;
• To complete the procedure, press the button for 2 s, the operator continues the previously interrupted operation
DIP1
Closure thrust.
Maintain the door wing in the closure position.
4
3
1
0
DIP2
Direction selection.
ON
The opening direction is intended by viewing the auto-
mation from the side being examined.
1 2 3
DIP3
Safety test terminal 41
TC
Automatic closing time. From 0 to 30 s.
Adjust the time that passes between the end of the opening operation and the start of the automatic closing operation.
The count is reset when an opening command is given with the door open.
0 s
disable
Adjust the TC to the maximum if automatic closing is not required.
DIP "WEIGHT"
Select wing weight for LOW ENERGY use
ON
1 2 3
LED
Acceso
Green
Power supply on
Red
Safety contacts 6 or 8 open.
Red + Green
Trimmer/dip switches adjustment
+
procedure enabling
Red + Green
/
Opening:
Press quickly to activate the opening operation
ENABLING of trimmer/dip switches adjustment:
(red+green LEDs on, see enabling procedure)
6. REQUISITES FOR DOORS FOR LOW ENERGY USE
The OLLY C automation is factory supplied with maximum performance setting. If used with the Low Energy service, the "Weight" dip switches must
be selected according to the weight of the door wing, as shown in the following table.
NB: consider the weight of a single door wing.
Attention: an incorrect setting of the dip with respect to the weight of the door leads to an incorrect speed and consequent operation inconsistent
with Low Energy use.
ON
1 2 3
DIP "WEIGHT"
DIP1
DIP2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
1 2 3
DIP "WEIGHT"
DIP1
DIP2
Any configuration
Description
Description
Encoder not working or automation faulty.
Safety test failure.
• 2 flashes = trimmer/dip switches adjustment confirmed
• 4 flashes at 1s intervals, indicates that an adjustment has been made without first ena-
bling the adjustment procedure:perform the enabling procedure again.
Alternately flashing light
the automation is stopped due to coinciding opening and closing commands
DIP3
Weight of a door wing
Up to a max 40kg (1 door)
OFF
or 2 x 27kg (2 doors)
Up to 25kg
OFF
From 26 → 30kg
OFF
From 31 → 35kg
OFF
From 36 → 40kg
ON
DIP3
Weight of a door wing
Up to a max 40kg (1 door)
or 2 x 27kg (2 doors)
OFF
Disabled.
Righthand opening.
Automation with 2 door wings
Disabled The safety sensors are not monitored and the
NC contacts must be connected to terminals 1-6 and 1-8
See chapter 6
Flashing light
Opening speed
0,40m/s
0,36m/s
0,34m/s
0,31m/s
0,29m/s
Closing speed
0,20m/s
17
Enabled
Lefthand
opening
Enabled
OFF
ON
See chapter 6
Performance
Maximum performance,
NO Low Energy
Low energy
performance
DO NOT USE
Performance
Low Energy performance
ON