Status Codes
Status codes
Sending of errors
-
-
Code Description
906
Heating element 1 faulty -
short circuit L1
907
HE 1 - Overload on L2
908
HE 1 - Overload on L3
909
HE 1 faulty - L1 highly re-
910
sistive
911
HE 1 faulty - L2 highly re-
sistive
HE 1 faulty - L3 highly re-
sistive
912
HE 2 faulty - short circuit
L1
913
HS 2 - Overload on L2
914
HE 2 - Overload on L3
915
HE 2 faulty - L1 highly re-
916
sistive
917
HE 2 faulty - L2 highly re-
sistive
HE 2 faulty - L3 highly re-
sistive
918
Relay 2 faulty
919
Relay 3 faulty
920
TS short circuit
921
TS not connected or faulty
922
60 °C for legionella pre-
vention could not be
achieved within 24 hours.
923
Minimum temperature
could not be achieved wit-
hin 5 hours
924
ES could not achieve mini-
mum temperature within 5
hours.
Errors are saved in the Datamanager 2.0 and can be sent via Solar Web.
Possible error outputs (as at 07/12/2015):
Cause
The load on L1 is higher than 3 kW. Short
circuit on L1.
Current on L2 greater than 16 A.
Current on L3 greater than 16 A.
No current is flowing through L1/L2/L3.
L1/L2/L3 of HE 1 faulty. Phase L1/L2/L3
interrupted.
The load on L1 is higher than 3 kW. Short
circuit on L1.
Current on L2 greater than 16 A.
Current on L3 greater than 16 A.
No current is flowing through L1/L2/L3.
L1/L2/L3 of HE 2 faulty. Phase L1/L2/L3
interrupted.
Relay R2/R3 sticking.
TS input resistance less than 200 Ohm.
No PT1000 TS connected. TS defective.
No TS connected (input resistance greater
than 2000 Ohm). TS is activated (should
be deactivated). TS cable defective. TS
defective. No PT1000 TS connected.
ES is switched off/faulty. (922 only). TS
has not been fitted correctly. Heating sys-
tem has not been dimensioned properly
(hot water consumption too high, etc.).
HE/TS faulty.
ES switched off/defective. ES not connec-
ted to Ohmpilot. TS incorrectly mounted.
Heating system not dimensioned properly
(hot water consumption too high, etc.). TS
faulty.
Remedy
Check heating element 1.
Check wiring.
Check HE 1 and replace if
necessary.
Check L1/L2/L3. Check
L1/L2/L3 connections.
Check HE 2. Check wi-
ring.
Check HE2 and replace if
necessary.
Check L1/L2/L3. Check
L1/L2/L3 connections.
Replace Ohmpilot.
Check cable and connec-
tions on TS cable. Re-
place TS.
Connect TS to device. De-
activate TS via the web-
site (if sensor not nee-
ded). Check TS cable.
Replace TS.
Switch on ES (922 only).
Fit TS above the HE (in
the protective tube). De-
activate legionella preven-
tion via the website. Re-
place HE/TS.
Switch on ES. Connect
ES to relay 1. Fit TS abo-
ve the heater battery of
the ES. Check minimum
temperature setting. Re-
place TS.
113